KILO

KILO M

1

TERMS OF WARRANTY

The warranty is valid 3 years starting from the manufacturing date, as evidenced on the receipt
of the calibration certificate, for the period indicated on the package.
The warranty covers the free repair or substitution of equipment parts which are recognized as
faulty due to manufacturing defects.
The warranty does not cover those parts which result defective due to negligent or improper use,
incorrect installation or maintenance, operation by unauthorized personnel, damage during
transportation, or which in any case do not indicate manufacturing defects of the equipment. Also
excluded from the warranty are technical interventions regarding the installation of the equipment.
Also excluded from the warranty are technical interventions regarding the installation of the
equipment to the electrical system.
The manufacturer declines any responsability for eventual injury or damage to persons, animals
or things as result of failure to follow the instructions in the Instructions Manual or caused by
improper use of the equipment.
The warranty covers equipment returned ex works. The expenses of transport as well as the relative
risks of same, both to and from the place of repair, will be the sole responsability of the User.
This warranty expires  after the date of purchase and any assistance required after said date
including spare parts, labor, transport of personnel and materials will be charged to the User
basated on the tariffs in force for Technical Assistance Service at the time of such requested service.
In any case the substitution of the equipment as well as the extension of the warranty after such
breakdown is excluded.

The packaging of each instrument bears a "CE" mark of conformity.

2

SAFETY

This instrument was manufactured and tested in compliance with class 2 IEC EN61010 and VDE
411 standards, in accordance with group C VDE 0110 standards for operating voltages up to 500
VACrms. Quality and accuracy are guaranteed by an ISO9000 certified production structure
which utilizes the latest surface mounting techniques, therefore the instrument left the factory in
perfect condition regarding technical safety.
In order to maintain this condition and to ensure safe operation, the user must comply with the
indications and markings contained in the following instructions:
When the instrument is received, before beginning installation, check that it is still intact and no
damage was incurred during transport.
Before mounting, ensure that the operating voltage and mains voltage set are the same, and then
proceed with installation.
The instrument unit is double insulated and does not require an earth connection. The power supply
must be connected to phase and neutral as shown in the relevant diagram.
A 50 mA T type HBC fuse should be installed in the power supply circuit to the instrument.
The power supply must be connected before the measurement circuit.
Before any maintenace and/or repairs, whenever the instmrument  must be opened, it must be
disconnected from all power sources.
The instrument’s capacitors may still be charged even after it has been disconnected from all
power sources.
Maintenance and/or repairs must be carried out only by qualified, authorized personnel.
If  there is ever the suspicion that safe use is no longer possible, the instrument must be taken out
of service and precautions taken against accidental use.

Operation is no longer safe when:
- There is clealy visible damage.
- The instrument no longer functions.
- After lengthy storage in unfavorable conditions.
- After serious damage incurred during transport.

2.1

OPERATOR SAFETY

Read these pages carefully before installing and utilising the instrument

The instrument described in this user manual is intended for use by properly trained staff only.
Maintenace and/or repairs must be carried out only by authorized personnel.

For proper, safe use of the instrument and for maintenace and/or repair, it is essential that the
persons instructed to carry out these procedures follow normal safety precautions.

2.2

SYMBOLS

READ THE INSTRUCTIONS

2.3

DIMENSIONS AND TECNICAL CHARACTERISTICS

 

Inputs:

Voltage

: 500V  20 to 800 Hz

Current

: 5 A  20 to 800 Hz

 Power Supply:

200÷240 VAC ± 10% 50/60 Hz
100÷120 VAC ± 10% 50/60 Hz  (on request)

• 

Temperature Range:

 -10°C to +60°C

• 

Storage Temperature:

 -25°C to +80°C

200 ÷ 240 VAC

 50 mAT

Max 500 VAC

Fase-Fase

Max 500 VAC

Fase-Neutro

Fig. 1

Fig. 2

Fig. 3

Fig. 4

P1

P1 P1

Wire passages

3

POWER SUPPLY

The instrument must have a power supply with voltage ranging from 200 ÷ 240  VAC  50/60 Hz
(100 ÷ 120 VAC 50/60 Hz is also available on request) using max. cable gauge 4 mm

 and

attached to the power supply terminals (see Fig.1).
The instrument’s power supply does not need an earth connection.
The instrument requires the installation of an external 50 mA type HBC fuse in the power supply
circuit.

3.1

VOLTAGE MEASUREMENT CONNECTIONS

For the voltage measurement connection use wires with max gauge 4mm

2

. Insert the wires in

the screw terminals for the voltage measurement connection.

3.1.1 3 wires delta connection (

?

)

The diagram  in Fig.2 indicate how  to connect the terminals to the phases on unbalanced three-
phase systems without neutral (DELTA).

3.1.2 4 wires STAR CONNECTION  (

Y

 )

The diagrams in Fig. 3 indicate how to connect the terminals to the phases on unbalanced three-
phase systems  with neutral (STAR).

The detailed wiring diagrams to the network are given in chapter 3.

3.2

CURRENT MEASUREMENT CONNECTIONS

The instrument is equipped with three wire passages through which the current wires must be
passed without having to interrupt them. Insert the wires as indicated in  Fig.4  (instructions as
to how to insert the current wire are also found on  the instrument’s label in correspondence with
the wire passages). The P1 and P2 indications identify the correct direction of the current.
Wires with max. 7 mm external diameter are permitted.

Advanced Function:

 If the instrument has been programmed for Cogeneration functioning, it

is absolutely essential that the sense (orientation) of the current direction be observed.

4

WIRING DIAGRAMS

4.1

CONNECTION ON UNBALANCED THREE-PHASE 3 WIRE  DELTA

NETWORKS (

?

)

          

Voltage Signal Connection

Corrent Signal Connection

Fig. 5

Fig. 6

English

Instructions

95

90

62

41

10

58

45

157,5

Содержание KILO

Страница 1: ...rs whenever the instmrument must be opened it must be disconnected from all power sources The instrument s capacitors may still be charged even after it has been disconnected from all power sources Maintenance and or repairs must be carried out only by qualified authorized personnel If there is ever the suspicion that safe use is no longer possible the instrument must be taken out of service and p...

Страница 2: ...current output as indicated in the drawings Fig 7 1 and 7 2 Advanced Functions If the instrument has been programmed for Cogeneration mode connection of the CTs must be carried out as indicated in the drawings in Fig 10 1 and Fig 10 2 located on the next page 4 2 CONNECTION ON UNBALANCED THREE PHASE 4 WIRE NETWORKS The drawing in Fig 10 indicates how to make the current connections with 3 CTs 4 2 ...

Страница 3: ...e set flashing The key enables moving from one digit to another from the more significant digit to the less significant digit Once the last digit is set this key enables programming of the transformation ratio of the VT and access to the next programming page 6 1 3 CONNECTION TYPE SELECTION STAR OR DELTA Selecting VOLT LOW on the first programming page or after setting the VT ratio having selected...

Страница 4: ...to be set flashing The key enables moving from one digit to another from left to right Once the last digit is set it enables confirmation of the programming and to access to the selection page of the surveyed temperature measurement unit 6 2 6 WEEK DAY SETTING This function is available on KILO M only ad it is fundamental for recording in memory the weekly consumtion The data are stored in memory ...

Отзывы: