background image

The power outlets of the ePowerSwitch-8M+ Master and its 4 
satellite units can be controlled using a simple ASCII protocol 
over an RS232 serial connection.

1.Use  the  provided  RS232  serial  cable  to  connect  the 
ePowerSwitch-8M+ to an available serial port of your PC. 

2.Run a terminal program such as Windows HyperTerminal or 
the MicroTerminal program on the CD.

3.Configure  the  appropriate  serial  port  with  the  following 
settings: 9.600 bauds, 8 bits, no parity, 1 stop bit and no flow
control. 

4.On  your  computer,  press  <ENTER>  until  the  configuration 
menu appears on your screen. 

Syntax of the command line:   

/Pxy=z

(this command line MUST start with a slash)

Example to control the Master:

/P00=1 

<ENTER> 

switch all the 8 power outlets ON

/P00=0 

<ENTER> 

switch all the 8 power outlets OFF

/P04=r  

<ENTER> 

restart power outlet 4

/P08=t  

<ENTER> 

toggle power outlet 8

Example to control the first satellite unit connected to the 
ePowerSwitch-8M+ Master:
DIP-Switch of the Satellite: 1 to 4 = off

/P10=1 

<ENTER> 

switch all the 8 sockets ON

/P15=0 

<ENTER> 

switch socket 5 OFF

5. Command through a serial connection

NETWORK INTERFACE PARAMETERS

:

IP address on LAN is 192.168.100.100
LAN interface's subnet mask is 255.255.255.0
IP address of default gateway to other networks
is 192.168.1.2

MISCELLANEOUS:

HTTP Port is 80
Finder program is enabled.
HTTP config is enabled.

HARDWARE PARAMETERS:

MAC Address is 00.13.F6.01.1D.A3

Parameter Value

Function

X

0 to 4

represents the address of the unit:
0 = ePowerSwitch-8M+ Master
1 = ePowerSwitch-8XS Satellite #1
2 = ePowerSwitch-8XS Satellite #2
3 = ePowerSwitch-8XS Satellite #3
4 = ePowerSwitch-8XS Satellite #4

y

0

all 8 outlets are controlled together with 1 command

1 to 8

number of the power outlet you want to control

z

0

Command to switch the socket(s) Off

1

Command to switch the socket(s) On

r

Command to restart the socket(s)

t

Command to toggle the state of the socket

Remarks:

The ePowerSwitch accepts lower case and upper case commands.
The ePowerSwitch sends an echo for each received character.
If the Twin mode is activated, sending a command to a specific socket 
number will also control its corresponding twin socket.

ePower

ePower

Switch

Switch

8M+

8M+

© Copyright

All rights reserved

ELECDAN 

2 impasse de la noisette 

Parc GVIO 

91370 VERRIERES LE BUISSON 

FRANCE

Tél. +33 (0) 1 60 11 44 44 
Fax +33 (0) 1 69 20 39 63
www.elecdan.com 

[email protected]

July 2010

Quick Start Guide

ePower

Switch

8M+

Master is a power control unit with a built-in Web server and 

an Ethernet connection. It enables you to control the power supply of eight power 
outlets remotely over IP (Intranet or Internet) or an RS232 Terminal connection.

The number of the controlled sockets can be extended up to 40 by cascading up 
to four ePowerSwitch 8XS Satellite units.

Thanks to the use of two separate power inputs and the optional Twin mode which 
allows you to control  at the same time two power outlets, this device is the ideal 
solution for power management of servers with redundant power supplies.

It  also  enables  you  to  monitor  8  IP  devices  (servers,  routers,  cameras...)  and 
automatically reboot them in the event of lock-up.

Before operating your ePowerSwitch, please read 
the  safety  instructions  in  the  User  Guide  on  the 
provided CD-ROM.

1. Installation

Connect the ePowerSwitch-8M+ to your Local Area Network.
Power-up the ePowerSwitch through properly grounded sockets.

Содержание ePowerSwitch 8M+

Страница 1: ...llite 3 4 ePowerSwitch 8XS Satellite 4 y 0 all 8 outlets are controlled together with 1 command 1 to 8 number of the power outlet you want to control z 0 Command to switch the socket s Off 1 Command to switch the socket s On r Command to restart the socket s t Command to toggle the state of the socket Remarks The ePowerSwitch accepts lower case and upper case commands The ePowerSwitch sends an ech...

Страница 2: ...connected to the network if you disconnect the network cable of the ePowerSwitch 8M the monitoring functions stop The PING rule is used to check if a computer or any IP device is connected to the network The SCAN rule is used to check if a specific protocol is available on a server for example HTTP FTP Telnet SMTP POP 3 IP device monitoring After configuring the network parameters using one of the...

Страница 3: ...doit être précédée d un slash Exemple de commandes destinées au Master P00 1 ENTER met toutes les 8 prises secteur sur ON P00 0 ENTER met toutes les 8 prises secteur sur OFF P04 r ENTER restart de la prise 4 P08 t ENTER toggle la prise secteur 8 Exemple de commandes destinées au premier satellite connecté à l ePowerSwitch 8M Master DIP Switch du Satellite 1 à 4 off P10 1 ENTER met toutes les 8 pri...

Страница 4: ...difiez momen tanément les paramètres réseau de votre PC en fonction des paramètres réseau par défaut de l ePowerSwitch Adresse IP 192 168 100 100 Port 80 Passerelle 255 255 255 0 1 Démarrez votre navigateur et saisissez l adresse IP de votre ePowerSwitch 2 Saisissez le nom et le mot de passe administrateur admin par défaut pour les deux La page d accueil apparaît et vous permet de configurer votre...

Отзывы: