Page
12
Setting: Max. Load
NB:
This function only operates if a frequency converter is used to control the
inlet conveyor.
When using this function, move the cable in clamp XD3 to XD1 on the control
panel. (See the circuit diagram page 21).
The Max. Load MPR setting is used to regulate input to the MPR. If a Max.
Load is set, the MPR will try to maintain the set loading value.
Method of operation:
If the load is greater than the set value, the MPR will reduce the speed of the
input and if the load is less it will increase the speed of the input.
Max. Load
The Percentage view can be adjusted by pressing the UP/DOWN buttons.
The setting range is 0-100%.
Percentage
0
setting
Adjustment
UP/DOWN
UP
DOWN