AEM33 V 485 DIN 

 

INSTRUCTIONS 

 

 

 

This instrument is manufactured in compliance with EN61010-1 

Cat III for nominal operating voltages of 400V L-L and 230V L-N, 

to  ensure  safe  operation  the  user  must  comply  with  the 

following instructions: 

 

Ensure that the supply voltage is correct. 

 

The  auxiliary  mains  supply  is  internally  fused  at  250V, 

100mA  Type  2.  External  fusing  is  required  if  the  auxiliary 

supply voltage exceeds 250V. 

 

Maintenance  and/or  repairs  must  be  carried  out  only  by 

qualified, authorised personnel. 

 

If  there  is  ever  the  suspicion  that  safe  use  is  no  longer 

possible,  the  instrument  must  be  disconnected  and 

precautions must be taken against accidental use. 

 

Operation is no longer safe: 

1)

 

If there is clearly visible damage 

2)

 

If the instrument no longer functions 

3)

 

After prolonged storage in unsuitable conditions. 

 

 

 

 

 

Read  these  instructions carefully  before  installing  and  utilising 

the instrument. 

The  instrument  described  in  this  user  manual  is  intended  for 

use by properly trained staff only.  Maintenance and/or repairs 

must be carried out by authorised personnel only.  For proper, 

safe use of the instrument and for maintenance and/or repair, 

it  is  essential  that  the  persons  instructed  to  carry  out  these 

procedures follow normal safety precautions. 

 

 

 

 

 

CAUTION

:  Failure  to  follow  the  instructions  may  result  in 

personal injury or damage to equipment. 

 

 

NOTE

:  Failure  to follow  the  instructions may result  in 

an instrument malfunction. 

 

 

 

 

 

 

 

 

 

 

 

Current Sensor Installation 

The following diagram shows how each device is fitted on the cable 
for correct operation: 

 

 

 

The  secondary  cables  should  be  wired  with  the  correct  polarity.  
The  white  cable  (or  black/white)  is  the  negative  and  should  be 
connected  to  S2  or  CT-  on  the  meter.    The  black  cable  is  the 
positive and should be connected to S1 or CT+ on the meter.  

NOTES: 

 

 

The output from these current sensors is a low voltage.  It 
is safe to leave these outputs open-circuit if not connected 
to a meter.  

 

The  output  connections  from  these  current  sensors  must 
be individually wired direct to the meter and must not be 
earthed or connected to any other circuit.  

 

If  the  sensor  secondary  cables  require  extending  the 
following instructions apply: 

 

Cables  may  be  extended  to  a  total  distance  of  25  metres 
provided the following restrictions are observed. 

 

Cable must be twisted pair, screened, min 22AWG.  

Recommended type is Belden 8451 or equivalent. 

 

Cables should be mounted away from AC power cabling.  

Outside the main enclosure, separate containment or a 

separation of >100mm is recommended. 

 

NOTE

: Above cable is rated at 300V.  Additional 

containment may be required if running inside panels with 

exposed conductors. 

 

 

 

 

Current sensor polarity is irrelevant in 

Auto CT Rotation 