background image

ELKM43

CONTROLLER AND  

MINI-PROGRAMMER

Quick guide

ELKM43-GB-06-05-B

EL.CO. S.r.l.

Via Lago di Molveno, 20 - 36015 Schio (VI) 

ITALY

Tel.: +39 0445 661722 - Fax: +39 0445 661792

www.elco-italy.com

e-mail: [email protected]

Preface

This manual contains the information necessary for 

the product to be installed correctly and also in-

structions for its maintenance and use; we therefore 

recommend that the utmost attention is paid to the 

following instructions and to save it.

This document is the exclusive property of eL.cO. S.r.l. 

which forbids any reproduction and divulgation, even 

partially, of the document, unless expressly authori-

zed. eL.cO. S.r.l. reserves the right to make any formal 

or functional changes at any moment and without 

notice.
eL.cO. S.r.l. and its legal representatives do not assume 

any responsibility for any damage to people, things or 

animals deriving from violation, wrong or improper 

use or in any case not in compliance with the instru-

ment features.

Whenever a failure or a malfunction of the control 

device may cause dangerous situations for persons, 

thing or animals, please remember that the plant 

has to be equipped with additional safety devices.

1.  dIMeNSIONS aNd cuT-OuT (mm)

controller with non removable terminals

48

48

48

11

14

Panel cut-out

65 mm min.

45

+0.6

 mm

45

+0.6

 mm

65 mm min.

Mounting requirements

This instrument is intended for permanent installa-

tion, for indoor use only, in an electrical panel which 

encloses the rear housing, exposed terminals and 

wiring on the back.  Select a mounting location having 

the following characteristics:
1.  It should be easily accessible;
2.  There is minimum vibrations and no impact;
3.  There are no corrosive gases;
4.  There are no water or other fluids (i.e. condensation);
5.  The ambient temperature is in accordance with the 

operative temperature (0... 50°c);

6.  The relative humidity is in accordance with the 

instrument specifications (20... 85%);

The instrument can be mounted on panel with a 

maximum thickness of 15 mm.
When the maximum front protection (IP65) is desired, 

the optional gasket must be mounted.

2.  eLecTrIcaL cONNecTIONS

eLecTrIcaL cONNecTIONS

RS485

Thermo-

couple

DI1

OP3

OP2

OP1

OP4

(note)

DI2 (note)

Analogue input

mV, V

mA

12 VDC

(note)

PV

4... 20 mA

3 wire transmitter

12 VDC

(note)

PV

Pt100

Pt1000/NTC/PTC

4... 20 mA

2 wire transmitter

Neutral

Line

Power

supply

Terminals

Pin: 

q

1.4 mm max. (0.055 in.)

Stropped wire: L: 5.5 mm (0.21 in.)

L

Note:  Terminal 4 can be programmed as:

 - digital Input (dI2) connecting a free of voltage 

contact between terminals 4 and 16;

 - 0... 12 V SSr drive Output (OP4) connecting the load 

between terminals 4 and 16;

 - 12 Vdc (20 ma) transmitter power supply connect-

ing the 2 wire transmitter between terminals 4 

and 1; for 3 wire transmitter connect terminal 

4 to transmitter power supply input and termi-

nal 1 and 2 to transmitter signal output.

Power supply voltage: 100... 240 Vac/20... 30 Vdc/ 

 

18... 28 Vac/24... 240Vac/dc;

Out1 relay:  4 (4) a/250 Vac, SPST;
Out2, 3 relay: 2 (1) a/250 Vac, SPST Na (*) ;
Out1, 2, 3 SSr: 10 Vdc/15  ma;
Linear Out1:  0/4... 20 ma, 0/2... 10 V;
Out4 SSr: 

12 Vdc/20 ma.

* for 

eLKM43 servodrive models both Out2 and Out3 

are to be selected as “M” in configuration code; 

Out2: open, Out3: close.

General notes about wiring

1.  Safety regulations require a line switch marked as 

instrument disconnecting device.  This switch must 

be easily reachable by the operator;

2.  do not run input wires together with power cables;
3.  external components (like zener barriers, etc.) con-

nected between sensor and input terminals may cause 

errors in measurement due to excessive and/or not 

balanced line resistance or possible leakage currents;

4.  When a shielded cable is used, it should be con-

nected at one point only;

5.  Pay attention to the line resistance, a high line 

resistance may cause measurement errors.

6.  To avoid electrical shocks, connect power line at last;
7.  Before connecting the instrument to the power 

line, make sure that line voltage is equal to the 

voltage shown on the identification label;

8.  The power supply input is NOT fuse protected. 

Please, provide an external fuse T type 1a, 250 V.

3.  cONfIGuraTION PrOcedureS

Setting the parameters

Press the       key

 

for 3 seconds

Access to

parameters

Insert

password 

(default: 30)

PV

AT

PV

AT

PV

AT

Key

editing Mode

confirm and go to Next parameter

Increase the displayed value or select the next element

decrease the displayed value or select the previous element

exit from Operator commands/Parameter setting/configuration

How to exit the “configuration mode”

To exit from the configuration mode,  

press the 

 key for 3 seconds.

code configuration procedure

for eLKM43 version (without timer and programmer) a 

simplified code configuration method is available. Only 

essential functions can be set up with code configura-

tion procedure. See the “engineering user Manual” for 

more details.

4.  LIST Of THe ParaMeTerS (

pAss

: 30)

]

inP Group - Main and auxiliary input configuration

no. Par.

description

dec.

Values

default Notes

SenS

Model c

Tc J 

(-50... +1000°c/-58... +1832°f);

craL Tc K 

(-50... +1370°c/-58... +2498°f);

Tc S 

(-50... 1760°c/-58... +3200°f);

Tc r 

(-50... +1760°c/-58... +3200);

Tc T 

(-70... +400°c/-94... +752°f);

Ir.J  exergen IrS J (-46... +785°c/-50... +1445°f);

Ir.ca  exergen IrS K (-46... +785°c/-50... +1445°f);

Pt1  rTd Pt 100 (-200... +850°c/-328... +1562°f);

Pt10 rTd Pt 1000 (-200... +850°c/-328... +1562°f);

0.60  0... 60 mV linear;

12.60 

12... 60 mV linear;

0.20  0... 20 ma linear;

4.20  4... 20 ma linear;

0.5  0... 5 V linear;

1.5  1... 5 V linear;

0.10  0... 10 V linear;

2.10  2... 10 V linear.

J

Model e

Tc J 

(-50... +1000°c/-58... +1832°f);

craL Tc K 

(-50... +1370°c/-58... +2498°f);

Tc S 

(-50... 1760°c/-58... +3200°f);

Tc r 

(-50... +1760°c/-58... +3200);

Tc T 

(-70... +400°c/-94... +752°f);

Ir.J  exergen IrS J (-46... +785°c/-50... +1445°f);

Ir.ca  exergen IrS K (-46... +785°c/-50... +1445°f);

Ptc  PTc KTY81-121 (-55... +150°c/-67... +302°f);

ntc  NTc 103-aT2 (-50... +110°c/-58... +230°f);

0.60  0... 60 mV linear;

12.60 

12... 60 mV linear;

0.20  0... 20 ma linear;

4.20  4... 20 ma linear;

0.5  0... 5 V linear;

1.5  1... 5 V linear;

0.10  0... 10 V linear;

2.10  2... 10 V linear.

2

dp

decimal Point Position (linear inputs)

0

0... 3

0

decimal Point Position (non linear inputs)

0/1

3

SSc Initial scale read-out for linear inputs

dp -1999... 9999

0

4

fSc

full Scale readout for linear inputs

dp -1999... 9999

1000

5

unit engineer unit

°c/°f

°c

6

fil

digital filter on the measured value

1

0 (= Off)... 20.0 s

1.0

7

ine

Sensor error used to enable the safety output 

value

or 

Over range;

ur 

under range;

our 

Over and under range.

our

8

oPe Safety output value (% of the output)

-100...  100

0

9

IO4.f I/O 4 function

on 

Output used as PWS for TX;

out4  Output 4 (digital output 4);

dG2c  digital input 2 driven by contact;

dG2u  digital input 2 driven by voltage.

out4

9

IO4.f I/O 4 function

on 

Output used as PWS for TX;

out4  Output 4 (digital output 4);

dG2c  digital input 2 driven by contact;

dG2u  digital input 2 driven by voltage.

out4

10 dif1 digital Input 1 function

off  Not used;

 

alarm reset;

  2 

alarm acknowledge (acK);

  3 

Hold of the measured value;

  4 

Stand by mode;

  5 

Manual mode;

  6 

Heat with SP1 and cooL with SP2;

  7 

Timer ruN/Hold/reset;

  8 

Timer run;

  9 

Timer reset;

 10 

Timer  run/Hold;

 11 

Timer  run/reset;

 12 

Timer run/reset with lock;

 13 

Program  Start;

 14 

Program  reset;

 15 

Program  Hold;

 16 

Program  run/Hold;

 17 

Program  run/reset;

 18 

Sequential SP selection;

 19 

SP1 - SP2 selection;

 20 

SP1... SP4 binary selection;

 21 

digital inputs in parallel to 

 / 

 keys.

off

12 di.a digital input action (dI2 only if configured)

  0 

dI1 direct action, dI2 (if configured) direct action;

  1 

dI1 inverse action, dI2 (if configured) direct action;

  2 

dI1 direct action, dI2 (if configured) inverse action;

 3  dI1 inverse action, dI2 (if configured) inverse 

action.

0

]

Out group - Output parameters

no. Par.

description

dec.

Values

default Notes

13 o1t

Output 1 type (when Out 1 is a linear 

output)

0-20  0... 20 ma;

4-20  4... 20 ma;

0-10  0... 10 V;

2-10  2... 10 V.

0-20

14 o1f

Out 1 function (when Out 1 is a linear 

output)

0

None  Output not used;

H.reG  Heating output;

c.reG  cooling output;

r.inP  Measure retransmission;

r.err 

error (SP - PV) retransmission;

r.SP 

Set point retransmission;

r.Ser  Serial value retransmission.

H.reG

Out 1 function (when Out1 is a digital 

output)

0

None  Output not used;

H.reG  Heating output;

c.reG  cooling output;

aL 

alarm output;

t.out  Timer output;

t.Hof  Timer out -Off in hold;

P.end  Program end indicator;

P.HLd  Program hold indicator;

P.uit 

Program wait indicator;

P.run  Program run indicator;

P.et1  Program event 1;

P.et2  Program event 2;

or.bo  Out of range or burn out indicator;

P.faL  Power failure indicator;

bo.Pf  Out of range/burn out/Power failure indicator;

St.bY  Stand by status indicator;

dif.1 

The output repeats the digital input 1 status;

dif.2 

The output repeats the digital input 2 status;

on 

Out 1 always ON;

riSP 

Inspection request.

15 ao1L Initial scale for the analog retransmission dP -1999 ... ao1H

-1999

16 ao1H full scale for the analog retransmission dP ao1L ... 9999

9999

17 o1aL alarms linked up with the out 1

0

0... 63:

 +1 

alarm  1;

 +2 

alarm  2;

 +4 

alarm  3;

 +8  Loop break alarm;

 +16  Sensor  Break;

 +32  Overload on output 4.

1

18 o1ac Out 1 action

0

dir 

direct action;

reu 

reverse action;

dir.r 

direct with reversed Led;

reu.r  reverse with reversed Led.

dir

19 o2f Out 2 function

0

See O1f - Out 1 function (digital output)

aL

20 o2aL alarms linked up with the out 2

0

See O1aL - alarms linked up with the out 1

1

21 o2ac Out 2 action

0

See O1ac - Out 1 action

dir

22 o3f Out 3 function

0

See O1f - Out 1 function (digital output)

aL

23 o3aL alarms linked up with the out 3

0

See O1aL - alarms linked up with the out 1

2

Содержание ELKM43

Страница 1: ...for 3 seconds Code configuration procedure For ELKM43 version without timer and programmer a simplified code configuration method is available Only essential functions can be set up with code configura tion procedure See the Engineering User Manual for more details 4 List of the parameters pAss 30 inP Group Main and auxiliary input configuration no Par Description Dec Values Default Notes SEnS Mod...

Страница 2: ...th Active in both cases both rEG Group Control parameters no Par Description Dec Values Default Notes 56 cont Control type 0 Pid PID heat and or On FA ON OFF asymmetric hysteresis On FS ON OFF symmetric hysteresis nr Heat CoolON OFFcontrolwithneutralzone 3Pt Servomotor control Pid 57 Auto Autotuning selection 0 4Oscillatingauto tunewithauto restartatpowerON and after all point change 3Oscillating ...

Страница 3: ...d value Whennoprogramisrunning theinstrumentshowsthe standard display P t tu When the programmer is running the display shows thetotalelapsedtime Atprogramend theinstrument alternately displays P End and the measured value P t td Whentheprogrammerisrunning thedisplayshowsthetotal remainingtime countdown Atprogramend theinstru mentalternatelydisplaysP Endandthemeasuredvalue ti uP Whenthetimerisrunn...

Страница 4: ...essage shows that a short circuit is present on Out 4 when it is used as ou tput or transmitter power supply When the short circuit disappears the output restarts to operate NoAt Auto tune not finished within 12 hours ErEP Possible problem in the instrument memory The message should automatically disappear if the error persists send the instrument to your supplier RonE Possible problem of the firm...

Отзывы: