PacDrive™ M
field bus PROFIBUS-DP
page 71
8.2 Electrical Connections
Ko
rr
ek
tu
ra
us
dr
uc
k
8.2
Electrical Connections
The PROFIBUS optional module has a 9-pole D-sub socket for
connection to PROFIBUS.
X11-PROFIBUS
Table 8-5: Connections PROFIBUS optional module
Connector plug
The lines must be connected via the PROFIBUS connector plug,
since this plug contains the bus closing resistors.
The possible PROFIBUS connector plugs with different cable
lengths are shown below.
Fig. 8-1: PROFIBUS connector plugs
Pin
Designation
Meaning
Range
max. cross
section
1
SHIELD
earth connection
(shield)
0,25 mm
2
2
-
not used
0,25 mm
2
3
RxD/TxD-P
received/transmitted
data - P (B / B´)
RS 485
0,25 mm
2
4
CNTR-P
control signal P
TTL
0,25 mm
2
5
DGND
PROFIBUS data
receive potential (C /
C´)
0,25 mm
2
6
VP
supply voltage Plus
5 V +/- 10 %
0,25 mm
2
7
-
not used
0,25 mm
2
8
RxD / TxD-N
receive/transmitted
data - N(A / A´)
RS 485
0,25 mm
2
9
-
not used
0,25 mm
2