background image

 

technical and operational documentation

 

Doc. version: 3.0.100

 

Содержание FPM+

Страница 1: ...technical and operational documentation Doc version 3 0 100 ...

Страница 2: ...EPSCUS 25 7 3 e UPS 25 7 4 LSK 26 7 5 e LSK 29 7 6 SKC A 29 7 7 FPM bus repeater 32 8 MAIN HOUSINGS FOR CONTROL UNIT MODULES 33 8 1 EPSCUS 33 8 2 LSK 33 8 3 SKC 33 8 4 SKC A 34 8 5 Main housing of the control unit type FPM M YY ZZ 34 8 6 FPM X YY ZZ 35 8 7 FPM U x x x x x and FPM L x x x x x 36 8 8 Plastic multiple module housings 36 9 ASSEMBLY INSTRUCTIONS 40 9 1 Bus 40 9 2 Shielding 40 9 3 Exter...

Страница 3: ... 12 24 Input function smoke detector warning 46 12 25 Input function evacuation with firefighting action 46 12 26 Input function general alarm 46 12 27 Input function pressure control 46 12 28 Input function external temperature sensor 46 12 29 Input function internal temperature sensor 47 12 30 Input function upper pressure sensor 47 12 31 Input function bottom temperature sensor 47 13 OUTPUT FUN...

Страница 4: ...X YY ZZ HOUSINGS 57 19 1 FPM 2 YY ZZ 57 19 2 FPM 4 YY ZZ 59 19 3 FPM 6 YY ZZ 61 19 4 FPM 8 YY ZZ 63 19 5 FPM 10 YY ZZ 65 20 APPENDIX C FPM U X X X X X AND FPM L X X X X HOUSING SPECIFICATIONS 67 21 APPENDIX D FPM U X X X X X AND FPM L X X X X HOUSINGS DRAWINGS 68 21 1 FPM U 4 6 0 A D 68 21 2 FPM U 4 6 18 A G 69 21 3 FPM U 4 6 0 B D 69 21 4 FPM U 4 6 18 B G 70 21 5 FPM U 6 6 0 A D 70 21 6 FPM U 6 6...

Страница 5: ...ices fire alarm receiving equipment damage alert receiving system evacuation lighting systems internal standpipes and standpipe valves external standpipes pumps in fire water pumping stations fire dampers smoke extraction equipment explosion prevention and containment equipment smoke curtains and doors fire doors and other fire rated closures if fitted with control systems fire emergency power shu...

Страница 6: ...R module is unique among all the unit modules This is the main module of the unit with the function of overseeing the exchange of information between the other modules and the exchange of information between the control unit and the higher level system BMS firefighting equipment integration system The MASTER module with additional control unit handling items buttons and indicator lights is always ...

Страница 7: ...Page 6 of 78 Fig 2 Control unit topology diagram ...

Страница 8: ...e a flame retardant cable can be used The general rule is that if at least one system or one appliance connected to the FPM must be operating during a fire FPM action at the time of fire must be assured Therefore the bus and controller power supply installations must be wired in non flammable cables Connections to appliances and systems should be wired with a cable adequate for the requirements pr...

Страница 9: ...erial numbers 4 2 LENGTH OF BUS BETWEEN MODULES The bus is divided into sections Each module on the bus is the end and the start of the respective sections to which it is connected The length of sections between specific modules should not exceed 1200 meters 4 3 LENGTH OF MP BUS The overall length of a single MP Bus connecting 8 actuators with a single LSK module should not exceed 600 meters 4 4 N...

Страница 10: ...mensions as per the control unit documentation Firmware version FPMplus Manual auto options Automatic through a signal from the fire alarm system control panel smoke extraction system control panel or automatic smoke detectors of the fire alarm system Manual trigger with the smoke extraction button Manual control from the integrating system Systems and appliances integrated with the control unit F...

Страница 11: ...x power consumption 2A 24VDC excluding power supply to appliances such as actuator holders etc Internal operating voltage 24 48VDC Power supply type or other identification CAMELEON ZM24V24A 600PZ C Operating temperature range 25 70 C Housing protection grade n a installed in multiple module IP42 housing Dimensions L x W x H 262x111x66mm With connections 279x111x66mm Main power supply supply volta...

Страница 12: ...s supervised with the option of switching off supervision NO NC mode Typical line resistance values Supervision state 1kΩ Alarm state 3 3kΩ Analog inputs Analog inputs for signal acquisition 4 20mA with external resistor 0 5V direct 0 10V with external resistor Max inputs Digital monitored 504 Digital analog configurable 1008 for EPSCUS 2016 for e LSK Recommended cable types For control unit bus n...

Страница 13: ... with varying flammability classifications use highest rated cables out of the applicable requirements to build the bus Cables must be provided with relevant approval documents for use in fire protection installations Certificate of conformity Certificate of Approval by CNBOP PIB Scientific and Research Center for Fire Protection National Research Institute Supply voltage 24 48VDC IP n a installed...

Страница 14: ...DC control output MP Bus 1 e LSK MODULE DESCRIPTION Supply voltage 24 48VDC VAC IP IP 20 for the module itself IP 42 for steel housings module installed in FPM multiple module housing IP 42 for ABS housings module installed in same housing as SKC A Maximum power consumption 2 4W 24VDC In out lines System bus 2x EIA 485 RS 485 standard galvanically isolated MP BUS 2 x MP BUS standard System bus vol...

Страница 15: ...talled in same housing as EPSCUS Maximum power consumption 2 4W 24VDC In out lines System bus 2x EIA 485 RS 485 standard galvanically isolated Inputs 16 x Outputs 8 x relays System bus voltage 5VDC Max bus current in supervised state 50mA typical 0 05mA Dimensions 214 x 108 x 62 mm In ABS housing 252 x 202 x 90 mm Weight ca 400 g In ABS housing 1100 g ...

Страница 16: ...tem BMS SMS Fitted with Ethernet port two RS485 ports an RS232 port eight relay outputs and eight inputs The communication ports as well as two 5A VDC relays are installed on the main board of the module while the inputs and the six additional 1A 30VDC outputs are located on the extension board Module inputs are used to monitor and control the unit managing lights buttons access key The main unit ...

Страница 17: ... for shutting down voice alarms Reset button for a fire reset triggered from access level 2 Power light indicates that the unit is powered and working Malfunction light indicates that the unit has discovered a malfunction Fire light indicates that the unit is in the fire state Locked light indicates that the unit has certain components in locked state ...

Страница 18: ...d the LSK module can also control and monitor analog equipment items e g fire damper actuators In order to support such devices the LSK must be connected to SKC A module The LSK module is also fitted with four potential free signal inputs These inputs can operate in supervised NO or NC modes For the purpose of receiving alarm signals from the FAS an input should be configured in line supervision m...

Страница 19: ...SK module no trip inputs in e LSK there are 4 trip inputs in an LSK module different installation method by default e LSK should be installed in a multiple module housing of the FPM unit on a DIN bus bar while LSK is installed in a separate housing The primary method of installation of an LSK module is to place it in a multiple module housing of the FPM unit while an e LSK can be installed in a se...

Страница 20: ... of analog values from different types of detectors is referenced as EPSCUS A An EPSCUS module can be placed in the main housing together with the MASTER module max 2 items in one of the steel housing versions OZ FPMPLUS xx or OBZ FPMPLUS xx in an ABS housing for a single module EPSCUS modules are installed in multiple module housings on a DIN bus bar The choice of the specific housing and number ...

Страница 21: ...upporting cables with core diameters up to 2 5mm2 28 12AWG closed DIN bus bar enclosure EPSCUS modules are installed in FPM unit housings on a DIN bus bar Installation in an additional ABS housing is also possible such as the housing for EPSCUS module The choice of the specific housing and number of modules in a housing depends on the building design and the need to build a control system for fire...

Страница 22: ...ed for transmission at 230VAC 24VDC voltage relay output or as a potential free output only The module is configured in terms of output signal 230VAC voltage 24VDC voltage potential free signal by the manufacturer Such setup can also be done by a trained service operative In such case the manufacturer is not responsible for service personnel errors Identification of SKC A module According to modul...

Страница 23: ...uts with very large distances between modules and in high interference environments primarily at industrial sites The FPM bus repeater module is manufactured by MOXA as TCC 120I module but will be tuned by the control unit manufacturer to the operating parameters of the FPM control unit bus The control unit manufacturer cannot warrant proper operation of the bus if a TCC 120I module is used withou...

Страница 24: ... If the control unit generates an alert of loss of bus continuity Check the power supply to FPM bus repeater module s Check the connection between the FPM bus repeater module and other FPM unit modules Check the connections between other FPM unit modules Damage to the bus is indicated by a joint damage alert DAMAGE indicator light on the unit s control panel in the visualization system and in FPM ...

Страница 25: ... layout for an FPM unit Fig 12 FPM unit power supply connector and bus layout Table 2 Identification and functions of FPM X YY ZZ housing ITEM IDENTIFICATION FUNCTION 1 230VAC L Power supply 230V L wire 2 230VAC N Power supply 230V N wire 3 PE Power supply 230V protective wire 4 24 VDC Internal FPM power supply 24 VDC 5 0 VDC Internal FPM power supply 0 VDC 6 ELA BUS1 A ELA BUS1 A 7 ELA BUS1 B ELA...

Страница 26: ...ors Vcc 24VDC power supply polarity GND power supply 24VDC polarity AINx is the identification of an input interface no x and GND is the input neutral shared with power OC type inputs are identified as follows OC11 OC12 OC13 OC21 OC22 OC23 EARTH terminals are used for connecting cable shields Fig 13 EPSCUS module connectors 7 3 E UPS e USP modules are installed in multiple module housings FPM X YY...

Страница 27: ... inputs should be connected to a specific module the following gland chokes should be removed For gland identified as 4 on the drawing when WE3 and or WE4 input is used For gland identified as 5 on the drawing when WE2 and or WE1 input is used Glands should be tightened with significant force so that they have no slack in the housing however the installer should be careful not to damage the glands...

Страница 28: ...ctive Yellow green Green NOTE For your own safety this operation should be performed after shutting down 230V 50Hz power supply 7 4 2 CONNECTING FIRE DAMPERS The LSK module is designed to operate with dampers fitted with MP BUS actuators Connect the MP Bus control cable on LSK side to the interface identified as MP BUS To do this draw the fire damper connection cable through gland no 3 then press ...

Страница 29: ...ntering the housing separately then press the A B and SHIELD terminal levers with a flat blade screwdriver width 3 4mm and insert the separate cable cores into the corresponding terminals Terminal colors correspond to YnTKSY cable core colors to facilitate the connection blue to blue white to white shielding to green Fig 19 Connecting ELA BUS lines in LSK 7 4 4 CONNECTING WE1 WE4 TRIGGER INPUTS Fi...

Страница 30: ... LSK module is fitted with two control unit bus inputs at the bottom of the housing on both sides and two MP BUS bar inputs left upper section of the housing Module power supply is connected to the two terminals in the right upper section of the housing Fig 22 Connection of e LSK module 7 6 SKC A The diagrams below present the main methods of connecting SKC A modules to power supply and to the con...

Страница 31: ...Page 30 of 78 Fig 23 SKC A to control unit and power supply wiring diagram Fig 24 SKC A to control unit and power supply wiring diagram ...

Страница 32: ...Page 31 of 78 Fig 25 SKC A to control unit and power supply wiring diagram ...

Страница 33: ...Page 32 of 78 7 7 FPM BUS REPEATER An FPM bus repeater module is powered with 24VDC voltage It is fitted with two ports for connecting ELA BUS Fig 26 FPM bus repeater module connection diagram ...

Страница 34: ...r 12 48VDC Power can be supplied from a certified fire rated power supply In the selection of cable thickness for connections power consumption and voltage drops should be considered Power can be supplied from a certified fire rated power supply Follow the guidelines for installation to maintain a proper level of security and to avoid interference with the protection level Each module must be perm...

Страница 35: ...fixed permanently 8 5 MAIN HOUSING OF THE CONTROL UNIT TYPE FPM M YY ZZ The main housing of the control unit and the basic multiple module housings are designed on the basis of single range steel cabinets This ensures identical housing attachment technique connection tightness and effective installation of fixtures The differences between the specific types of housings are concerned with dimension...

Страница 36: ...size of a specific housing it can accommodate different numbers of modules and therefore it offers different numbers of unit inputs and outputs Item ENCLOSURE SYMBOLS MAX EPSCUS CONTROLLERS MAX INPUTS OUTPUTS 1 FPM 2 YY ZZ 2 12 x O C outputs 16 x relay outputs 16 x analog or digital inputs 2 FPM 4 YY ZZ 4 24 x O C outputs 32 x relay outputs 32 x analog or digital inputs 3 FPM 6 YY ZZ 6 36 x O C ou...

Страница 37: ... fit for installation of e LSK and e USP modules Detailed specifications of the housings are presented in Appendix 3 and assembly drawings of the housings are given in Appendix D 8 8 PLASTIC MULTIPLE MODULE HOUSINGS Multiple module plastic housings are designed to accommodate multiple modules and are available in three basic sizes They can be fitted with power supplies with different power ratings...

Страница 38: ...Page 37 of 78 Fig 29 CP5004 type housing ...

Страница 39: ...Page 38 of 78 Fig 30 CP5005 type housing ...

Страница 40: ...Page 39 of 78 Fig 31 CP5008 type housing ...

Страница 41: ... bus MP BUS must be made of shielded cables e g YnTKSYekw HTKSHekw It is further recommended to connect input signals to EPSCUS module inputs using shielded cables Shielding should be continuous connected to shared PE potential It is recommended to join ELA BUS shields together e g by twisting or connecting to appropriate terminals in the modules All steel housings FPMPLUS M xx xx OBZ FPMPLUS xx a...

Страница 42: ... EPSCUS modules A digital NO input is a digital input without line state supervision for direct connection of relay contact Open state is alerted as idle shorting means an alarm Fig 32 Digital NO input diagram 10 3 INPUT TYPE DIGITAL NC Digital NC inputs are present in LSK and EPSCUS modules A digital NC input is a digital input without line state supervision for direct connection of relay contact...

Страница 43: ...ent in EPSCUS modules A digital supervised NO input is a digital input with line state monitoring Monitoring is done via a connected NO contact that triggers resistor signal The resistance values are the following 3 3kOhm for idle 1kOhm for alarm This input indicates line failure if the line resistance value is outside these two values Fig 34 Digital supervised NO 2EOL NO input diagram 10 7 INPUT ...

Страница 44: ...nge use a resistor divider so as to avoid exceeding the 5V threshold An additional safeguard is used to protect the system against the consequences of exceeding the permitted voltage value Example function of an analog 0 5V input is for voltage supervision 10 9 INPUT TYPE ANALOG 4 20MA Analog 4 20mA inputs are present in EPSUS A modules Analog 4 20mA inputs accept 4 20mA signal where an additional...

Страница 45: ...output which can be used for example to connect an external resistor 11 2 OUTPUT TYPE OPEN COLLECTOR Open Collector outputs can be used for connecting indicator elements such as lights An external relay with 12V coil can be connected to an Open Collector output and in such case a flyback diode should be additionally used An EPSCUS module is fitted with six Open Collector outputs 11 3 OUTPUT TYPE A...

Страница 46: ... FIRE RESET A system reset input all the appliances will be reset to idle positions and the inputs actuators will return to ready state 12 8 INPUT FUNCTION FIREFIGHTING ACTION Firefighting action signal input Active state at this input indicates that additional relay outputs are operated in EPSCUS modules 12 9 INPUT FUNCTION TECHNICAL ALARM A general purpose input for connecting any external signa...

Страница 47: ...es to idle mode 12 22 INPUT FUNCTION MANUAL FIRE ALARM Manual input of a fire alarm from FACP for example using the control panel 12 23 INPUT FUNCTION SMOKE DETECTOR ALARM If an alarm is notified from a smoke detector during a fire a fan will be shut down If a smoke position is set for a damper it will switch to that position at this alarm 12 24 INPUT FUNCTION SMOKE DETECTOR WARNING If a warning i...

Страница 48: ... for fan action in the assigned zone 12 30 INPUT FUNCTION UPPER PRESSURE SENSOR Pressure measurement result in Pascals The result of measurement is responsible for fan action in the assigned zone 12 31 INPUT FUNCTION BOTTOM TEMPERATURE SENSOR Pressure measurement result in Pascals The result of measurement is responsible for fan action in the assigned zone ...

Страница 49: ...designed for shutting off and restarting power supply for appliances where such procedure is required duct sensors 13 8 OUTPUT FUNCTION INDICATOR LIGHTS An output for connecting an indicator light indicating a fire in the zone It will also respond to Light test input signal 13 9 OUTPUT FUNCTION FIRE ALARM An output to an external system communicating a fire occurring in the assigned zone 13 10 OUT...

Страница 50: ...N EXHAUST TOP This is an actuator function used in configuring a staircase and the reverse system These actuators are characterized by an alarm position changing during system operation depending on temperature These actuators can only be associated with the reverse zone 13 20 OUTPUT FUNCTION SUPPLY BOTTOM This is an actuator function used in configuring a staircase and the reverse system These ac...

Страница 51: ...en check the power supply to MASTER module connection Connect the MASTER module of the FPM unit to a PC with an Ethernet cable FPM Configurator servicing and diagnostic software as well as Tibbo DS Manager must be installed on the PC Start Tibbo DS Manager and see whether the PC can correctly detect the MASTER module of the FPM unit Otherwise check the Ethernet cable Check the IP address of the MA...

Страница 52: ...ntenance It is recommended to clean up the dust off the external surfaces of the unit 15 3 SAFETY PRECAUTIONS 15 3 1 INSTRUCTIONS FOR USE Failure to comply with the instructions in the user manual poses a risk of irreversible damage to the unit and can cause property losses injury and or death 15 3 2 PROTECTION AGAINST ELECTRIC SHOCK The FPM fire control unit is classified as Class I protection ra...

Страница 53: ...l Any repairs can only be done by the manufacturer Ela compil shall not be responsible for the functioning of equipment maintained or repaired by unauthorized personnel The specific maintenance requirements are defined for each building separately on the basis of the specific contract 15 3 5 FUSE REPLACEMENT When replacing fuses use substitutes of the appropriate type and rated value ...

Страница 54: ...port box 16 2 TRANSPORT REGULATIONS The modules in their original packaging should be transported in locked space of regular land transport vehicles taking into account the transport instructions indicated on the packaging protected from violent shock or ambient temperature below 25 C or above 55 C 16 3 STORAGE REGULATIONS Store the control unit all modules indoors at 0 C to 70 C 40 to 70 relative...

Страница 55: ... JULY 2006 AND ARE IN CONFORMITY WITH REGULATION OF THE MINISTER OF THE ECONOMY OF THE REPUBLIC OF POLAND OF 27 MARCH 2007 JOURNAL OF LAWS NO 69 ITEM 457 CONCERNING SPECIFIC RESTRICTIONS ON THE USE OF CERTAIN SUBSTANCES CAPABLE OF NEGATIVELY IMPACTING THE ENVIRONMENT IN ELECTRICAL AND ELECTRONIC EQUIPMENT Worn out products which are unfit for continued use should be handed over to a waste electric...

Страница 56: ... Fig 19 Connecting ELA BUS lines in LSK 28 Fig 20 Connecting WE1 WE4 trigger inputs in LSK 28 Fig 21 e LSK module in a plastic housing 29 Fig 22 Connection of e LSK module 29 Fig 23 SKC A to control unit and power supply wiring diagram 30 Fig 24 SKC A to control unit and power supply wiring diagram 30 Fig 25 SKC A to control unit and power supply wiring diagram 31 Fig 26 FPM bus repeater module co...

Страница 57: ... 8A 12A 16A 24A 17Ah 26Ah FPM M 0 0 2 FPM M 06A 17Ah 2 FPM M 16A 26Ah 2 FPM M 24A 26Ah 2 FPM 2 0 0 2 FPM 2 6A 17Ah 2 FPM 2 8A 17Ah 2 FPM 2 12A 26Ah 2 FPM 2 16A 26Ah 2 FPM 2 24 26Ah 2 FPM 4 0 0 4 FPM 4 6A 17Ah 4 FPM 4 8A 17Ah 4 FPM 4 12A 26Ah 4 FPM 4 16A 26Ah 4 FPM 4 24 26Ah 4 FPM 6 0 0 6 FPM 6 6A 17Ah 6 FPM 6 8A 17Ah 6 FPM 6 12A 26Ah 6 FPM 6 16A 26Ah 6 FPM 6 24 26Ah 6 FPM 8 0 0 8 FPM 8 6A 17Ah 8 F...

Страница 58: ... ZZ The FPM 2 YY ZZ is the smallest of all the available multiple module housings Its dimensions are 400x400x210 The housing can accommodate a maximum of two EPSCUS modules The housing can be fitted with an internal power supply or adapted to work with an external power supply ...

Страница 59: ...Strona 58 z 78 ...

Страница 60: ... YY ZZ Dimensions of the FPM 4 YY ZZ housing are 500x400x210 The housing can accommodate a maximum of four EPSCUS modules The housing can be fitted with an internal power supply or adapted to work with an external power supply ...

Страница 61: ...Strona 60 z 78 ...

Страница 62: ... YY ZZ Dimensions of the OBZ FPMPLUS 6 housing are 600x500x250 The housing can accommodate a maximum of six EPSCUS modules The housing can be fitted with an internal power supply or adapted to work with an external power supply ...

Страница 63: ...Strona 62 z 78 ...

Страница 64: ...YY ZZ Dimensions of the OBZ FPMPLUS 8 housing are 800x600x210 The housing can accommodate a maximum of eight EPSCUS modules The housing can be fitted with an internal power supply or adapted to work with an external power supply ...

Страница 65: ...Strona 64 z 78 ...

Страница 66: ... is the largest of FPM multiple module unit housings with the dimensions of 1000x600x250 The housing can accommodate a maximum of ten EPSCUS modules The housing can be fitted with an internal power supply or adapted to work with an external power supply ...

Страница 67: ...Strona 66 z 78 ...

Страница 68: ...0x600x250 FPM U 4 12 18 B G 600x600x250 FPM U 4 24 18 B G 600x600x250 FPM U 4 6 0 B D 600x600x250 FPM U 4 12 0 B D 600x600x250 FPM U 4 24 0 B D 600x600x250 FPM U 6 6 26 A G 800x600x300 FPM U 6 12 26 A G 800x600x300 FPM U 6 24 26 A G 800x600x300 FPM U 6 6 0 A D 800x600x300 FPM U 6 12 0 A D 800x600x300 FPM U 6 24 0 A D 800x600x300 FPM U 6 6 26 B G 800x600x300 FPM U 6 12 26 B G 800x600x300 FPM U 6 24...

Страница 69: ...atteries FPM U 4 6 0 with a cable tray layout A main tray in central location FPM U 4 6 0 A and cable glands in the bottom part of the housing FPM U 4 6 0 A D The housing can be fitted with 6A 12A or 24A power supply according to the selected option the respective field in the housing symbol will change A single e USP module or two e LSK modules can be installed in a single cell Dimensions of the ...

Страница 70: ...e or two e LSK modules can be installed in a single cell Dimensions of the housing 600x600x250mm 21 3 FPM U 4 6 0 B D The FPM U 4 6 0 B D is a universal housing with 4 installation cells FPM U 4 a power supply with max current 6A FPM U 4 6 without batteries FPM U 4 6 0 with a cable tray layout B trays around installation cells FPM U 4 6 0 B and cable glands in the bottom part of the housing FPM U ...

Страница 71: ...ule or two e LSK modules can be installed in a single cell Dimensions of the housing 600x600x250mm 21 5 FPM U 6 6 0 A D The FPM U 6 6 0 A D is a universal housing with 6 installation cells FPM U 4 a power supply with max current 6A FPM U 6 6 without batteries FPM U 6 6 0 with a cable tray layout A main tray in central location FPM U 6 6 0 A and cable glands in the bottom part of the housing FPM U ...

Страница 72: ...le or two e LSK modules can be installed in a single cell Dimensions of the housing 800x600x250mm 21 7 FPM U 6 6 0 B D The FPM U 6 6 0 B D is a universal housing with 6 installation cells FPM U 6 a power supply with max current 6A FPM U 6 6 without batteries FPM U 6 6 0 with a cable tray layout B trays around installation cells FPM U 6 6 0 B and cable glands in the bottom part of the housing FPM U...

Страница 73: ... to the selected option the respective field in the housing symbol will change A single e USP module or two e LSK modules can be installed in a single cell Dimensions of the housing 800x600x250mm 21 9 FPM L 8 6 0 A D The FPM U 8 6 0 A D is a housing dedicated to e LSK modules capable of accommodating max 8 modules FPM L 8 a power supply with max current 6A FPM L 8 6 without batteries FPM L 8 6 0 w...

Страница 74: ... glands in the upper part of the housing FPM L 8 6 18 A G Dimensions of the housing 600x500x250mm 21 11 FPM L 8 6 0 B D The FPM U 8 6 0 B D is a housing dedicated to e LSK modules capable of accommodating max 8 modules FPM L 8 a power supply with max current 6A FPM L 8 6 without batteries FPM L 8 6 0 with a cable tray layout B trays around installation cells FPM L 8 6 0 B and cable glands in the b...

Страница 75: ...f accommodating max 8 modules FPM L 8 a power supply with max current 6A FPM L 8 6 with 18Ah batteries FPM L 8 6 18 with a cable tray layout B trays around installation cells FPM L 8 6 18 B and cable glands in the upper part of the housing FPM L 8 6 18 B G Dimensions of the housing 600x500x250mm Power supply ...

Страница 76: ... 16 011 800 600 250 ZPAS WZ 2285 01 18 011 800 600 300 ZPAS WZ 2285 01 19 011 800 800 300 ZPAS WZ 2285 01 17 011 1000 600 250 ZPAS WZ 2285 01 20 011 1000 800 300 SZE2 CABINETS WITH SINGLE LEAF DOOR MANUFACTUR ER SYMBOL WIDTH HEIGHT DEPTH With integrated shielding With external shielding ZPAS WZ 1951 01 24 011 600 650 1800 500 ZPAS WZ 1951 01 23 011 600 650 1800 600 ZPAS WZ 1951 01 21 011 800 850 1...

Страница 77: ...0 800 300 RITTAL 1050 500 500 500 210 RITTAL 1350 500 500 500 300 RITTAL 1057 500 500 700 250 RITTAL 1039 500 600 380 210 RITTAL 1339 500 600 380 350 RITTAL 1060 500 600 600 210 RITTAL 1054 500 600 600 250 RITTAL 1360 500 600 600 350 RITTAL 1076 500 600 760 210 RITTAL 1376 500 600 760 350 RITTAL 1058 500 600 800 250 RITTAL 1090 500 600 1000 250 RITTAL 1260 500 600 1200 300 RITTAL 1077 500 760 760 ...

Страница 78: ...0 300 RITTAL 1019 600 1000 1200 300 RITTAL 1019 500 1000 1200 300 RITTAL 1101 120 400 400 250 RITTAL 1101 130 400 650 250 RITTAL 1101 140 650 650 250 KOMPAKT RITTAL CM SYSTEM HOUSINGS Manufacturer Symbol Width Height Depth RITTAL 5110 500 600 800 400 RITTAL 5111 500 600 1000 400 RITTAL 5112 500 600 1200 300 RITTAL 5113 500 600 1200 400 RITTAL 5114 500 800 1000 300 RITTAL 5115 500 800 1000 400 RITT...

Страница 79: ... 1800 400 RITTAL 5841 500 1200 1800 400 RITTAL 5842 500 1600 1800 400 RITTAL 5843 500 1200 2000 400 RITTAL 5844 500 1200 2000 500 RITTAL 5845 500 1200 2000 600 RITTAL 5846 500 1800 2000 500 SYSTEM CABINET SINGLE SE 8 STAINLESS STEEL MANUFACTUR ER SYMBOL WIDTH HEIGHT DEPTH RITTAL 5850 500 600 1600 400 RITTAL 5851 500 600 1800 500 RITTAL 5852 500 800 1800 500 RITTAL 5853 500 800 2000 600 RITTAL 5854...