El.Mo HEKLA Series Скачать руководство пользователя страница 1

111

User manUal

HEKLA sEriEs

Control panels and signalling equipment

1  

 DECLArATiON  OF  CONFOrMiTY 

AND PErFOrMANCE

20

no. 1328 – CPR – 0815

Standards: EN 54-2:1997/AC:1999/A1:2006

EN 54-4:1997/AC:1999/A1:2002/A2:2006

2  

 GENErALs

The fire alarm control panels HEKLA series control the de-

vices of a fire protection system, monitoring up to 384 dif-

ferent zones.

3  

 ACCEss  LEVELs

Panels functions can be accessed according to three differ-

ent access levels:

•  level 1 (public) – accessible to anyone via keypad

•  level 2 (user) – accessible with user access code via 

keypad

•  level 3 (maintenance/programming) – accessible with in-

staller access code via keypad

On level 1, access is granted just to functions that can be 

used by the public: 

•  Button Lamp Test

•  Area buttons Queue Review

Level 2 gives access to controls for authorized users: 

•  All other buttons

•  User menu

Access to level 2

 

– press ENTER

 

– enter the user access code (default)         

Note:  if you fail to enter the code within 10 seconds, the 

control panel returns to the previous screen.

 

– press ENTER

return to level 1

 

– press ESC until the date and time come up

4  

 FrONT  PANEL

The control panels can be controlled via the front panel on 

any fire alarm control panel, or a networked repeater panel. 

HEKLA  HLREPEATER 

All functions and statuses are viewed and managed via the 

graphic display and coloured indicator LEDs on the panel.

If there is an alarm or a fault, its description comes up on 

the display.

 

▼ Alarm message

Fire [progressive number] Zone [zone number] C [con-

trol panel address] L [loop number] D [device address] 

[device type]

[zone name][device name]

Last alarm zone [zone number]

Number of zones in alarm state [number]

 

▼ Fault message

Control panel [panel address]

[fault description]

Total number of faults [number]

If there is more than one alarm or fault message, the rele-

vant LED and/or flashes Fire  Fault 

 

– press the button by the LED to scroll through the list of 

alarms or faults

Once you have viewed all the alarms or faults present, the 

relevant LED stays steadily lit.