background image

1

Movement sensor  

with 180° detection area

Code: EK-SM2-TP 

KNX bus device for movement and presence detection 

in interior rooms. It has to be used in KNX installations 

for control of homes and buildings. 

Description

The movement sensor ekinex

®

 EK-SM2-TP is a KNX S-

mode device for the detection of movement and presen-

ce  of people in interior rooms with an detection area of 

180°. The device allows a energetically efficient control 

of the lighting and HVAC installations in residential, office 

and commercial buildings. The device is provided with 3 

passive infrared sensors (PIR) that can be separately ac-

tivated and allow an optimal 180° detection. The detection 

area can be extended using further sensors EK-SM2-TP 

configurated as slave devices. The light intensity for the 

constant brightness regulation is measured by the inte-

grated brightness sensor; the value can be furthermore 

sent on the bus as a Lux value (2 Byte). The channel 

dedicated to the HVAC application allows the indipendent 

control of heating, ventilation and air conditioning devi-

ces. The device has an integrated bus communication 

module and is realised for wall mounting; the metallic 

support allows the mounting on a round or square wall 

box with 60 mm distance between the fixing holes. The 

device is powered by the KNX bus line and requires no 

auxiliary power supply.

Operation 

The movement sensor reacts to the thermal radiation 

emitted by moving bodies. A person who walks in the 

detection area automatically activates the lighting. If the 

sensor no longer detects any movement, the lighting is 

switched off after the time delay set during the configura

-

tion with ETS

®

. If the standby mode is activated, the ligh-

ting remains switched on with a reduced intensity (orien-

tation light function) for the standby time set.

Datasheet STEKSM2TP_EN

Main characteristics

• 

Semi-automatic or fully automatic operation

• 

Detection range 180° (horizontal), 90° (vertical)

• 

Measuring range from 5 to 2000 Lux 

• 

3 PIR sensors can be activated individually or in groups 

• 

Sensitivity adjustable  (10 levels)

• 

Brightness sensor with linear output 

• 

High-resolution lens for detection of small movements 

•  Optical filter integrated

Other characteristics

• 

Housing in plastic material

• 

Wall mounting

• 

Protection degree IP20 (according to EN 60529)

•  Classification climatic 3K5 and mechanical 3M2 (accor

-

ding to EN 50491-2)

• 

Pollution degree 2 (secondo IEC 60664-1)

Technical data

• 

Rated voltage 24 Vdc (21 - 30 Vdc)

• 

Power absorption 0,4 W

Environmental conditions

• 

Operating temperature: - 20 ... + 40°C

• 

Relative humidity: 95% not condensing

Measurement of brightness

The measurement of the room brightness is carried out 

by an integrated light sensor with linear output and optical 

filter set on the profile of the human eye. The photoelec

-

tric sensor is able to send a 0 or 1 telegram, which indica-

tes a brightness level lower or higher than a programmed 

threshold value, independently from the operation mode. 

The brightness value, measured in Lux, can be transmit-

ted on the bus.

Lighting channel

The lighting channel has two operation modes that can be 

set in the configuration phase:
• 

fully automatic

• 

semi-automatic

The fully automatic mode has 3 states: ready, active and 

passive. The semi-automatic mode has 2 states: ready 

and active. The semi-automatic mode does not switch on 

the lighting after the movement detection, but only after 

the operation of an external pushbutton. 

HVAC channel

The HVAC channel has the same objects and functioning 

modes of the lighting function; but the movement detec-

tion is extended, as it is based on the «long duration» 

principle. The detection is carried out on several time win-

dows (from 2 to 20) of the same length in each of them at 

least one movement has to be detected. 

Device completing

For the installation and operation the sensor has to be 

completed with the separate order of:

• 

a lens with cover (see table below);

• 

a square plate with 55 x 55 mm window;

•  a square frame of the form or flank series.
The metallic support, the fixing screws and the terminal 

block for the connection to the bus line are included in 

the delivery. 

Отзывы: