Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 34
7.5
Weighted temperature value
The
Weighted temperature value
folder appears only if two sensors for measuring the room temperature
are enabled and includes the following parameters:
Main source for temperature value
Additional source temperature value
Relative weight
Minimum change of value to send [K]
Cyclic sending interval
7.5.1
Parameters and communication objects
Parameter name
Conditions
Values
Main source for temperature value
*
*) The values that can be set depend on enabling the internal sensor, the inputs or
the external sensors (from bus).
Additional source temperature value
*
*) The values that can be set depend on enabling the internal sensor, the inputs or
the external sensors (from bus).
Relative weight
100% main sensor
90% / 10%
80% / 20%
70% / 30%
60% / 40%
50% / 50%
40% / 60%
30% / 70%
20% / 80%
10% / 90%
100% additional sensor
Minimum change of value to send [K]
0,5
[other values in the range
0 … 5 K]
If the parameter is set to 0 (zero), no value is sent at the change.
Cyclic sending interval
no sending
[other values in the range 30 s … 120 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Weighted temperature
Cyclic sending interval different
than no sending
2 Byte
CR-T--
[9.001]
temperature °C
47
About the weighted temperature
The device allows the acquisition of the room temperature in three ways:
1)
from the temperature sensor integrated in the device;
2)
from an external temperature sensor connected to a device input configured as analogic (Inputs
Input 1 or 2 = [AI] room temperature sensor);
3)
via bus from another KNX device, e.g. from an ekinex pushbutton (External sensors (from bus)
Room temperature = enabled);