Parameter name
Conditions
Values [Default]
Auto / Semi-auto select
Device type = Master
Auto
Semi-auto
The automatic mode controls both switch-on and switch-off; the semi-automatic mode only controls
switch-off after a manual switch-on through the external control pushbutton.
HVAC switch-'ON' delay
Device type = Master
0...30 min
[1 min]
Sets the delay before the output is switched ON whenever movement is detected; this is required to
prevent immediate activation when a person is present in the coverage area for just a brief period of time.
HVAC delay time
Device type = Master
5 s...60 min
[5 min]
Sets the delay before the output is switched OFF whenever movement is no longer detected.
Behaviour at switching on
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output when movement / presence is detected and confirmed.
Behaviour at switching off
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output when absence of movement / presence is detected and confirmed.
13.5 Menus: Alarm function
Although not specified below, these options are only listed if the alarm function is active.
Parameter name
Conditions
Values [Default]
Duration of one switch-on
window
Device type = Master
0.5 s...60 min
[0.5 s]
Duration of the period in which the specified number of movements (see next parameter) must occur in
order to cause the alarm to be switched ON
Number of switch-on
windows
Device type = Master
0...100 min
[10]
Number of movements in the specified period (see previous parameter) that cause the alarm to be
switched ON
Duration of one switch-off
window
Device type = Master
0.5 s...60 min
[0.5 s]
Duration of the period in which the specified number of movements (see next parameter) must occur in
order to cause the alarm to be switched OFF
Number of switch-off
windows
Device type = Master
0...100 min
[10]
Number of movements in the specified period (see previous parameter) that cause the alarm to be
switched OFF
Behaviour at switching on
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output when the alarm status is switched to ON.