9.9.2 Humidification
The secondary folder
Humidification
includes the following parameters:
•
Operating modes where humidification is active
•
Relative humidity setpoint for humidification control [%]
•
Dehumidification control hysteresis [%]
•
Disable from bus
9.9.2.1
Parameter and communication object tables
Parameter name
Conditions
Values
Humidification function
disabled
cooling
heating
both cooling and heating
Parameter that selects the humidification function.
Humidity setpoint
Humidification ≠ disabled
35
[range 25 … 45 %]
Humidity hysteresis [%]
0,8 %
[other values in the range 0,5 … 4%]
Cyclic sending interval
no sending
[other values in the range 30 s … 120
min]
Disable humidification control from bus
no
/ yes
Signal from bus
Disable humidification control from bus =
yes
not inverted
/ inverted
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj. No.
Relative humidity setpoint for
humidification
2 Byte
CRWTU-
[9.007] humidity (%)
59
Humidification command
1 Bit
CR-T--
[1.001] switch
64
Humidification control disable
Disable
humidification
control from bus =
yes
1 Bit
C-W---
[1.002] boolean
65