Applicatio Manual
Universal Interface 4 DIN/NTC EK- CG2-TP
Revisione 1.0.0 - Aggiornato: 04/09/2017
© SBS S.p.A.
– Tutti i diritti riservati
MAEKCG2TP_EN
Pag. 41
9.1.11 Coupled: shutter or venetian blind
Parameter name
Conditions
Values
Long press time
Input x = coupled
Type = shutter or venetian blind
hh:mm:ss.fff
(
00:00:03.000
)
Minimum push time for a press in order to be recognized as a long press.
xA and xB use
Input x = coupled
Type = shutter or venetian blind
A up, B down
A down, B up
Blind mode
Input x = coupled
Type = shutter or venetian blind
enabled /
disabled
If blinds mode is enabled, the device sends “full movement” telegrams on long press and “step”
telegrams on short press; if it is disabled, the device sends “full movement” telegrams on long press
and “stop” telegrams on short press.
Lock function
–
Behaviour at locking
Input x = coupled
Type = shutter or venetian blind
none
up
down
Operation to perform when a locking command is received.
Lock function
–
Behaviour at unlocking
Input x = coupled
Type = shutter or venetian blind
none
up
down
Operation to perform when an unlocking command is received.