Description

The ekinex

®

 universal interface is a KNX S-mode device 

that can be used as input or output. Depending on the 

version, the device is provided with: 

 - inputs to connect to the bus devices with free-potential 

contacts or NTC passive temperature sensors;

 - output to control low-consumption LEDs.

The device is provided with an integrated bus commu-

nication module and is realized in a compact design for 

installation  in  flush-mounting  wall  boxes.  The  device  is 

powered by the KNX bus line with a SELV voltage 30 Vdc 

and does not require auxiliary power. The scanning volta-

ge for the input channels is produced by the device.

Versions

Code

Inputs

Outputs

(low-con-

sumption 

LEDs)

EK-CC2-TP

2 for potential-free contacts

2

EK-CD2-TP

4 for potential-free contacts

4

EK-CG2-TP

4 configurables Individually for 

potential-free contacts or NTC 

temperature sensors

4

Functionalities

Each input channel of the device can be programmed as  

[DI] to carry out the function of:
• 

on/off switching of single loads or group of loads;

•  detecting the state of signaling contacts (from safety 

devices, alarms, etc.);

•  recalling and saving of scenes;

•  sending values on the bus (temperature, brightness, 

etc.);

•  switching to forced operating mode (lock);

•  counting of impulses and switching cycles.

Main characteristics

•  Housing in plastic material

• 

Wall installation in flush mounting box or, with a 

mounting support, on 35 mm rail (according to EN 

60715)

•  Protection degree  IP20 (installed device)

• 

Classification climatic 3K5 and mechanical 3M2 (ac

-

cording to EN 50491-2)

•  Pollution degree 2 (according to IEC 60664-1)

•  Weight 20 g

•  Dimensions 43 x 43 x 16 mm (WxHxD

)

Technical data

•  Power supply 30 Vdc from KNX bus line

•  Current consumption < 10 mA
Environmental conditions
•  Operating temperature: - 5 ... + 45°C

•  Storage temperature: - 25 ... + 55°C

•  Transport temperature: - 25 ... + 70°C

•  Relative humidity: 95% not condensing

Accessories

Rail-mounting support
The device can be mounted on 35 mm rail (according to 

EN  60715)  with  the  support  EK-SMG-35  to  be  ordered 

separately.

EK-SMG-35

Universal interface

Codici:  EK-CC2-TP (2 IN, 2 OUT)

 

        

EK-CD2-TP (4 IN, 4 OUT )  

 

EK-CG2-TP (4 IN configurables, 4 OUT)

KNX bus device for connecting conventional (not KNX) switches, 

sensors or NTC temperature sensors (to the inputs) and/or low-

consumption LEDs (to the outputs). It has to be used in KNX 

installations for control of homes and buildings.

A couple of input channels can be programmed to carry 

out the function of:
•  dimming of lighting devices;

•  controlling drives for shading devices (such as shut-

ters, blinds, curtains, etc.).

Each output channel of the device can be programmed 

as [DO] for:
•  controlling low-consumption LEDs to be used as sta-

tus feedback, orientation nightlights, etc.

As an alternative to programming it as [DI], each input 

channel of the EK-CG2-TP version can be programmed 

as [AI] for:
•  measuring of the air mass temperature with a NTC pas-

sive temperature sensor (NTC 10 kΩ at 25 °C) to be 

connected to the input with possibility of sending the 

value on the bus

• 

2 points (ON / OFF) or proportional (PWM or con

-

tinuous) room temperature regulation. The device 

is provided with 2 conduction modes (heating and 

cooling) with switching via bus and 4 operating modes 

(comfort, standby, economy and building protection) 

with separate setpoints for heating and cooling. 

Automatic switching function of the operating mode 

depending on presence or opening windows. The re-

gulation may work with a weighted average of the two 

temperature values

REAEKCDG2TP