KNX-IP Interface
Product code: EK-BB1-TP
KNX-IP Router
Product code: EK-BC1-TP
KNX device with interface function to connect to the LAN
for programming and/or supervision of the KNX bus
system.
With IP Router version it is possible to connect multiple
KNX bus lines through the LAN with a two-way
communication. Suitable for KNX installations for control
of houses and buildings.
Description
The Ekinex® EK-BB1-TP IP interface realizes the
bidirectional data link between a PC or laptop and a KNX
system via LAN. The interface supports IP tunneling
protocol and enables addressing, setting parameters,
viewing and diagnosis of KNX devices via ETS. The
device has an integrated KNX bus communication
module and is designed for 35mm rail mounting. Power is
supplied via the KNX bus.
The Ekinex® EK-BC1-TP IP router realizes the
bidirectional data link between a PC or laptop and a KNX
system via LAN. The interface supports IP tunneling
protocol and enables addressing, setting parameters,
viewing and diagnosis of KNX devices via ETS.
The IP router also integrates the function of a line
coupler; telegrams can be exchanged between TP bus
lines through a bridge over TCP/IP. The device has an
integrated KNX bus communication module and is
designed for 35mm rail mounting.
Four LEDs show with precision the status of both KNX
and Ethernet bus lines; this helps to find common
communication problems caused to bus overload or
multiple transmission on both lines.
The device is powered by a 30 Vdc SELV voltage via the
KNX bus and does not require auxiliary power but, when
sizing the bus line, you need to consider this as a supply
equivalent to 4 devices of 10 mA.
Function
• Line coupler
• KNX bus status
• Ethernet bus status
• IP router sends telegrams from / to KNX from / to IP
network
• Programmable plant via software ETS® remotely (IP
router)
Main characteristics
• Housing in plastic material
• Mounting on 35 mm rail (according to EN 60715)
• Protection degree IP20 (according to EN 60529)
• Safety class II
• Weight 70 g
• 2 modular units (1 unit = 18 mm)
• Dimensions 36 x 90 x 70 mm (WxHxD)
Technical data
Connections
• 30 Vdc from KNX bus line
• Current consumption (from main bus line): about 38
mA
• RJ45 ethernet connector
Environmental conditions
• Operating temperature: - 5 ... + 45°C
• Storage temperature: - 20 ... + 60°C
• Transport temperature: - 20 ... + 60°C
• Relative humidity: 5 - 95% not condensing
Switching, display and connection elements
The line/area coupler is equipped with 4 LEDs and a
function pushbutton located on the front of the device, 1
bus terminal for KNX bus line, 1 RJ45 connector for
Ethernet LAN, a programming LED and a programming
pushbutton.
TP1
Datasheet STEKBBC1TP_EN
RE
A
E
K
B
B
C
1
T
P
DC
E
K
B
B
C
1
T
P
1. LAN status LED
2. KNX status LED
3. LAN traffic LED
4. KNX traffic LED
5. Not used
6. Not used
7. Programming LED
A. Ethernet connector
B. Function pushbutton
C. Programming pushbutton
D. KNX bus connector