background image

INSTALLATION AND SERVICE INSTRUCTIONS

WFAM-1C-U & WFAM-2C-U

LED Medium Wallpack Arch

 WARNING:

THIS PRODUCT CONTAINS CHEMICALS  KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS, AND/
OR OTHER REPRODUCTIVE HARM.  THOROUGHLY WASH HANDS AFTER INSTALLING, HANDLING, CLEANING OR OTHERWISE 
TOUCHING THIS PRODUCT.

 SAFETY PRECAUTION:  

Warning:

 Risk of fire and electrical shock!  Before beginning installation or service, disconnect the power by turning off the circuit 

breaker. Turning the power off by using the light switch is not sufficient to prevent electrical shock.  This floodlight is for outdoor use 
and should not be used in areas of limited ventilation or high ambient temperature.  All work should be performed by a qualified elec-
trician. This product must be installed in accordance with the applicable installation code by a person familiar with the construction 
and operation of the product and the hazards involved. 

 INSTALLATION:

 WIRING:

• LED units are multi-volt 120V-277V.  No additional tap wires are necessary.

When this fixture is used with a photocontrol unit, be sure that the photocontrol’s voltage requirement matches the circuit voltage.

TROUBLESHOOTING CHECKLIST: 

If the light does not work

 Check your power source. 

 Check electrical connections.

Direct mounting to junction box:

1. Fasten the mounting plate to a recessed outlet or other mounting

surface.  Use the integrated bubble leveler to ensure that the plate 
is level.

2. Splice the power leads from the back of the fixture to the branch cir-

cuit leads from the junction box.  Attach black to black (hot), white to 
white (neutral), and green to green (ground).  Push the splices into the 
junction box.

3. Align the fixture against the mounting plate and retighten the set

screws to secure the fixture in place.  

4. For wet locations, caulk between the rear housing and the mounting

surface to prevent water from entering the fixture from behind.

Wall-mounted wiring box with conduit feed:

1. Attach the wiring box to the desired location using the bolt holes

provided.

2. Remove the threaded plug(s) and route electrical conduit to the holes

desired.  Feed the branch circuit wires through the conduit into the 
wiring box.

3. Splice the fixture power leads to the power leads inside the wiring

compartment box – black to black (hot), white to white (neutral), and 
green to green (ground).

4. Align the fixture against the wiring box and tighten the set screws to

secure the fixture in place.  Take care to not pinch the power wires.

Pole mount using slip fitter, knuckle, or trunnion:

1. Splice the fixture power leads to the power leads inside the wiring

compartment box – black to black (hot), white to white (neutral), and 
green to green (ground).

2. Align the wiring box against the back of the fixture and tighten the set

screws to secure it in place.

Slip fitter:

1. Splice the fixture power leads to the branch circuit power leads and

push the splices inside the pole.

2. Silde the slip fitter onto the end of the pole, rotate to the desired posi-

tion, and tighten the set screws.

3. Unscrew the philips head screws in the side of the slip fitter and

remove the hinge plate.

4. Loosen the hex bolt inside the hinge, adjust the fixture to the desire

angle, and retighten.  Replace the cover.

Trunnion:

1. Mount the trunnion in place using the bolt holes provided.
2. Route the fixture waterproof cable to the interior of the pole using a

waterproof connector.  Splice the fixture power leads to the branch
circuit leads -- black to black (hot), white to white (neutral), and green
to green (ground).

3. Remove the adjustment screw in the trunnion hinge and adjust to the

desired angle.  Replace the screw.

Knuckle:

1. Splice the knuckle power leads to the branch circuit power leads and

push the splices inside the threaded hole.

2. Screw the knuckle into the threaded hole, rotate to the desired angle,

then tighten the mounting nut.

3. Loosen the allen head screw in the side of the knuckle hinge and

adjust to the desired angle, then retighten.

NOTE:

 The LED module is preinstalled and prepositioned. DO NOT OPEN 

the unit. DO NOT TOUCH THE SURFACE OF THE LEDS. 

CAUTION:

 This 

fixture must be mounted in the LENS DOWN position.

Remove the rear mounting plate by loosening the two allen head set screws from bottom of the plate.

Отзывы: