D = 20 ~ 40m

22R 5W

R

220R 5W

{

 

Manual

C.01/Nov2018

Flow Switches

 

Models for G 3/4” Port

FC Series

eicos.net

flowsensor.eicos.us

 | 

datasheets.eicos.us

 | 

videos.eicos.us

IMPORTANT !

YOU MUST CHECK BEFORE INSTALLATION

Questions? Call us BEFORE you install:

AC Current: 

Use

 

K8

*

 

Filter

 

in parallel with the coil (A1 A2) of a contactor or relay.

 

DC Current: 

Use 

KD

*

 

Filter 

in parallel with the coil (A1 A2) of a contactor or relay.

*

For sale on 

accessories.eicos.us

Direct connection 

to the 

sensor

Use

 22R 5W

*

 

resistor 

in series

Use

24Vdc Voltage

• 

AUXILIARY CONTACTOR (mini contactor) mind the distance:

• 

SOLENOID VALVE or POWER CONTACTOR:

 

 Use 

mini contactor

 or 

auxiliary relay

.

• ELECTRONIC EQUIPMENT: 

  › Interface relay/relay coupler: 

Use 

4K7 10W resistor. 

 

› Timing relay and frequency inverter:

 Use 

220R 5W

resistor.

Follow the instructions below to protect and extend the shelf life of the sensor:

20m

40m

Operation

! Never connect the 

sensor directly to a motor, 

pump, lamp or any other 

load over 20W.

Always use a contactor 

or relay.

• 

Liquids with solid particles and/or fouling

 require prior testing. Use 

filter before the Sensor to prevent the internal piston from locking. Not 

recommended for industrial water waste.

• 

Liquids  with  ferrous  and/or  magnetic  particles

  require  technical 

analysis:  the  Sensor  contains  magnetic  components  inside.  Use  a 

magnetic filter before the Sensor to avoid deposition/settling that will 

prejudice its operation.

The sensors work in all voltage and current ranges displayed in the table bellow:

Operating Voltage

Max. Switching Power Max. Switching Current

Peak Current

110Vac

20VA

0,2A

0,5A @20ms

220Vac

20VA

0,1A

0,5A @20ms

5Vdc

2,5W

0,5A

1A @20ms

12Vdc

5W

0,5A

1A @20ms

24Vdc

10W

0,5A

1A @20ms

24Vac:

 NOT recommended

Term of Warranty

 

 

On

 

datasheets.eicos.us

 

available technical specifications

For installations according to this guide:

 

02 (two) years warranty. 

Incorrect installation cancels the warranty.

 

All Sensors have been tested and approved during the manufacture process.

Typical Connection to Contactor

K8 Snubber Filter

 for 

electrical installation (AC) 

(included)

Snubber 

Filter

Installing the snubber filter extends the 

lifespan of the sensor’s electrical contact.

 

*

On

 

accessories.eicos.us

 

check models and prices of Filters

  

Electrical Contact of Sensors

 

- Attention to Install

Note:

 Reed Switches have reached over one million operations in tests with 

contactor and 

K8

*

 snubber filter

.

Reed Switch 20W/VA: Protect the Electrical Contact of your Sensor

Reed Switches are hermetically sealed contacts 

actuated by a magnetic field.

The life expectancy of a reed switch refers to a 

kind of load to be used. Reed Switches of the highest reliability are applied in 

our sensors, and their life expectancy can reach above two million operations. 

However, when they are switching lamps, inductive or capacitive loads, this 

number may decrease.

Switching Power

It is important to consider that the power specified by an electrical load is 

often referred to the permanent working state.

For higher power, use an auxiliary relay or contactor as recommended below, 

or similar.

This resistor dampens the peak voltage caused by the 

capacitance of cables and electronic equipment input. 

? Risk of failure (welding of the Reed Switch Contact) 

due to CAPACITANCE, which 

can occur depending on the distance and cable used in the connection to the contactor. 

K8

*

 

Filter mounted in 

parallel with the coil of an 

AC contactor, increases the 

contact life.

• Switching inductive loads

0.1µF 400V

PROTECTION PROCEDURES BELOW DESCRIBED CAN IMPROVE 

THE REED SWITCH PERFORMANCE

• Connecting the sensor to a contactor in long distances, use resistor:

• Connecting the sensor to an electronic equipment:

Important

: For installation with 

relay coupler

, use 4K7 10W resistor.

•Timing relay

•Frequency inverter

•Etc.

Flow Switches and Level Switches for liquids

KD

*

 

Filter mounted in 

parallel with the coil of a

DC relay, increases the 

contact life

.

BY448

or

 1N4007

Important

: For distances 

greater than 40m

, use 24Vdc voltage.

K8

*

K8

*

KD

*

+55 (15)

 3032.9190

+55 (15)

 3032.9190

Siemens 3RT1015 Contactor

Initial: 31.7VA

Rated: 5.1VA

Contactor

Contactor

K8

 for AC

KD

 for DC