• The CO alarm should be a horizontal distance of between 1m and 3m from the
potential CO source.
• If there is a partition in the room, the CO alarm should be located on the same side
of the partition as the potential source.
• In rooms with sloped ceilings, the CO alarm should be located at the high side of the
room (see fig 3).
300mm
150mm
1 to 3 m
1 to 3 m
DEAD AIR
DON'T LOCATE
HERE
CO Alarm
Figure 2.
Location in room with a fuel burning appliance