background image

Installation

All regulators generate considerable heat and depend on the 

natural draft air circulation for adequate cooling.  

It is important that ventilation openings not be obstructed. 

Mounting in a confined or poorly ventilated space should be 

avoided unless special provisions have been made  

for ventilation.

Hard-Wired Voltage Regulators

Hard-wired voltage regulators vary in size according to the 

output power and may be mounted in either a horizontal or 

vertical position.  If mounted in a vertical position (on a wall, 

for example), steel mounting hardware must be selected in 

accordance with Table 1 for a secure installation.  The wiring 

compartment should be at the top.  Regardless of position, 

the regulator should be located where contact with the hot 

surface of the transformer is unlikely.

For proper ventilation, allow a minimum of 12 inches of 

clearance above the unit and a minimum of 6 inches of 

clearance on each side.  Dimensions of the regulators and 

the morning brackets are presented in Figures 1, 2, 3, and 4.  

The specifications for the figures are listed in Table 3.

Hard-wired regulators must be connected to a branch 

circuit in accordance with local and national electrical 

codes.  Electrical connections are diagrammed in Figure 5.  

Proper wiring is determined by the Figure indicated from the 

regulator specifications in Table 3.

If operation from a 3-phase source is required, three  

hard-wired regulators may be wired in delta as shown in 

Figure 10.  

Table 2 gives the proper jumper configurations for needed 

input and output voltages.  Table 2 also defines the regulator 

connections in relation to the points diagrammed in Figure 6.  

Fusing and wire gauge size are detailed in Table 3.

Note: 

 Branch circuit protection must be located in the 

primary of each transformer!  

Not

 in the three-phase 

operation, fuses must be connected in the primary of each 

unit, not in the three-phase lines.

On 7.5 and 10 kVA models, the terminal block is located in 

the right unit.  Use only the front or right side knockouts of 

the right unit for conduit connections.  On 15 kVA models, 

the terminal block is located in the middle unit.  Use only the 

front knockouts of the middle unit for conduit connections.

Two or more models of the same rating may be connected 

with their input and output in parallel.  However, on models 

smaller than 5 kVA, do not parallel both 208 V (X4-X5) and 

240 VCT (X1-X2-X3).  This may damage the  

output windings.

Table 3

VA

Voltage Input

Voltage Output

Catalog

Number

OD

Dimensions

Approx. 

Shipping 

Weight 

(kg)

Input Voltage

Output Voltage

Required Circuit Protection / Minimum Gauge 90

C WIRE

Minimum Gauge 90

C WIRE

Dim. 

(cm)

Dim. 

(cm)

Dim. 

(cm)

Dim. 

(cm)

Dim. 

(cm)

Dim. 

(cm)

Dim. 

(cm)

Dim. H 

(cm)

110-120

220-240

380-415

110-120

220-240

380-415

110-120

220-240

120

110, 120, 220, 240,  380, 415

110, 120, 220, 240

63-23-612-8

A

23,11

18,90

11,43

13,67

12,07

10,48

5,53

0,79 X 1,75

8,08

3

1.5

0.8

1, 0

1, 0

1, 0

1,0

1,0

250

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-625-8

A

26,92

18,90

11,43

13,67

12,07

10,48

5,53

0,79 X 1,75

12,24

6

3

1

1, 0

1, 0

1, 0

1,0

1,0

500

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-650-8

A

33,66

16,21

19,69

22.86

20,64

14,30

9,12

0,79 X 2,06

18,14

10

6

1

1, 5

1, 0

1, 0

1,0

1,0

1000

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-710-8

A

45,57

16,21

19,69

22,86

20,64

14,30

14,83

0,79 X 2,06

28,12

15

10

3

2, 5

1, 5

1, 0

1,5

1,0

2000

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-720-8

B

44,65

23,72

26,82

32,38

29,84

10,69

12,70

1,12 X 1,75

50,81

30

15

10

6, 0

2, 5

1, 5

4,0

1,5

3000

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-730-8

B

67,72

23,81

26,90

32,38

29,84

15,39

9,29

1,12 X 1,75

72,59

45

25

15

16,0

4,0

2,5

6,0

2,5

5000

110, 120, 220, 240, 380, 415

110, 120, 220, 240

63-23-750-8

B

76,20

23,81

26,90

32,38

29,84

23,79

9,37

1,12 X 1,75

109,79

80

40

20

25,0

10,0

4,0

16,0

4,0

7500

220, 240, 380, 415

110, 120, 220, 240

63-23-775-8

C

71,12

23,81

62,23

65,55

63,02

18,71

9,37

1,12 X 1,75

176,94

-

60

30

16,0

6,0

-

25,0

10,0

10000

220, 240, 380, 415

110, 120, 220, 240

63-23-810-8

C

76,20

23,81

62,23

65,55

63,02

23,80

9,37

1,12 X 1,75

220,50

-

80

40

25,0

10,0

-

35,0

16,0

15000

220, 240, 380, 415

110, 120, 220, 240

63-28-815-8

D

76,20

23,81

91,44

97,15

76,20

23,81

91,44

97,15

349,35

-

110

60

50,0

16,0

-

45,0

25,0

50 Hz Mini/Micro Computer Regulator (MCR)

Installation and Operation Manual

Figure 5:  

7500 VA and 10000–15000 VA  

Electrical Connections

Table 1: 

Bolt Sizes

Rated VA of Regulator

Minimum Recommended Size  

of Steel Mounting Hardware  

125/250

M6

500/1000

M7

1500 to 10000

M8

150000

M12

Operating & Service Instructions

Sola Minicomputer Regulators  

UL White Card Listed – Power Supply Classification  

CSA Certified – Transformer Classification

General Description and Specifications

The Sola Micro/Minicomputer Regulator (MCR) provide 

virtually instantaneous voltage regulation, and isolation from 

both transverse and common mode noises for any type 

of load. It also suppresses transients with ferroresonant, 

protects overloads, and serves as a dedicated line. It is the 
ultimate in AC power conditioning equipment.

Operating Temperature Range:  

-20° to +50°C.

Phase:  

Single

Input Voltage and Frequency:  

See Table 3

Output Voltage and Frequency:  

110/120/220/240 VAC

Output Voltage Regulation:  

+3% for an input line variation of 

+15%

Output Harmonic Distortion:    

Less than 3% total RMS content at 

full load.

Efficiency:

   85% or 90% at full load typical. No loss of output for 

line loss of 3 msec.

Noise Reduction:   

Common mode noise rejection exceeds 120dB. 

  

 Transverse noise rejection exceeds 60dB.

Voltage Surge Suppression:    

Meets  

ANSI/IEEE C62.41 

Category A and B waveforms  

(formerly IEEE 587-1980).

Figure 1:

Outline

Drawing 1

Figure 2:

Outline

Drawing 2

Primary Voltage

Interconnect Connect Lines To

220-240

H1 to H3

H2 to H5  

H1 & H5

380-415

H2 to H3  

H1 & H4

Secondary Voltage Interconnect Connect Lines To

110

X1 & X2 or X2 & X3

120

X4 & X2 or X5 & X2

220

X1 & X3

240

X4 & X5

MCR 50 Hz 7500 VA

Primary Voltage

Interconnect Connect Lines To

220-240

H2 to H3

H1 & H4

380-415

H2 to H3 

H1 & H5

Secondary Voltage Interconnect Connect Lines To

110

X1 & X2 or X3 & X2

120

X4 & X2 or X5 & X2

220

X1 & X3

240

X4 & X5

MCR 50 Hz 10000 - 15000 VA

Figure 3:

Outline

Drawing 3

Figure 4:

Outline

Drawing 4

Figure 6.

  

3-Phase Connections

*  Connect Per Table 2

Table 2: 

Wire and Jumper Configurations

Unit (VA)

Input Volts 

Input 

Terminals 

Jumper 

Connection 

Output 

Connection

250 to 5000

90-130

H1-H4

(H1-H3)

(H2-H4)

(All Models) 

110-X1-X2 or 

X2-X3 

120 X4-X2 or 

X2-X5 

220-X1-X3                   

240 X4-X5 

180-260

H1-H4

(H2-H3)

310-450

H1-H5

(H2-H3)

7500

180-260

H1-H5

(H1-H3)              

(H2-H5)

310-450

H1-H4

(H2-H3)

10000 to 15000

180-260

H1-H4

(H2-H3)

H1-H5

(H2-H3)

3

2

1

6

5

4

7

9

8

Отзывы: