![EG Xcellerex XDUO 2500 Скачать руководство пользователя страница 225](http://html1.mh-extra.com/html/eg/xcellerex-xduo-2500/xcellerex-xduo-2500_operating-instructions-manual_2367561225.webp)
7.6
Control the temperature
Introduction
The temperature of the disposable bag contents is controlled using the temperature
control unit (TCU).
The temperature control can be set to work in Auto or in Manual mode.
•
In Auto mode, the PLC controls the temperature of the disposable bag contents to
the setpoint (SP).
•
In Manual mode, the PLC sends the manually defined CV value (%) to the TCU. The
TCU calculates a setpoint (SP), using the configured range that is specific for the TCU
model.
Work in Auto mode
To set the temperature control to work in Auto mode follow the instructions below.
Action
Step
On the home screen, tap pH/Cond to open the pH and conductivity overview
screen.
1
Make sure that no interlocks are active.
2
Note:
The button is selected when an interlock is active.
Tap HOME to go back to the home screen.
3
Tap Temperature on the home screen to open the Temperature Detail
screen.
4
Xcellerex XDUO 2500 Mixer Operating Instructions 29146667 AH
225
7 Operation
7.6 Control the temperature