208-277VAC/60Hz
INSTALLATION AND OPERATING INSTRUCTIONS TO SET ON
AND OFF TIMES: Light trippers turn ON. Dark trippers turn OFF.
Place tripper on dial edge as shown in figure and set point of
each tripper to desired operating time. Note if selected time
is AM or PM. Hold tripper against dial edge and firmly tighten
knurled screw.
INSTALLATION AND OPERATING INSTRUCTIONS TO SET DIAL
TO TIME:
Turn dial counter-clockwise until correct time is
indicated by arrow on nameplate.
FOR TEMPORARY MANUAL OVERRIDE: Press down lever on right of nameplate to turn ON. Press down
lever on left of nameplate to turn OFF. CAUTION: Do not rotate dial for manual override.
TO REMOVE MECHANISM FROM CASE: Press lever near the top of the case, and pull the mechanism
out of the metal box. To replace, insert main plate projections in slots opposite latch and push in
mechanism until it latches.
O
F
F
O
N
TIM
E
ON TIME
(Light Tripper)
MANUAL
ON
LEVER
MANUAL
OFF
LEVER
OFF TIME
(Dark Tripper)
Knurled Screw
Dial Calibrations
15328 - 24 HOUR TIME SWITCH
SWITCH: DPST
CONTACT RATINGS:
120-277 V ac, 40 A Resistive, Single Phase
120-277 V ac, 40 A General Purpose, Single Phase
120-277 V ac, 20 A Ballast (Inductive)
120 V ac, 40 A Tungsten
120 V ac, 2HP
240 V ac, 5HP
TIMING MOTOR: 208-277 VAC 60Hz
POWER CONSUMPTION: 3 Watts MAX
GE5367-41K2
YYWW
15328 VERSION 1
12/27/12
WWW.JASCOPRODUCTS.COM
CONNECTIONS
2
X
1
L
O
F
F
O
N
2
X
L
H
H
1
LOAD
M
Typical for same voltage in LOAD and MOTOR
2
X
L
H
H
N
1
LOAD
LOAD
M
240V Motor and 120V Load
• Recommended installation by licensed electrician.
• High Voltage (There may be more that one source
of supply) disconnect all power sources before
servicing.
• Risk of electric shock – All terminals are live.
• Use copper wire only.
• Close the cover after setting.
• Tighten connections to 25 lbf-in.
• Use correct gauge wire (8-14 AWG) based on local
electrical code of at least 105C rating.
• Wire strip length ½"
• GROUNDING: National Electrical Code requires
that grounding must be continuous and in proper
electrical contact in all grounding conductors,
metallic conduits and grounding terminals.
MECHANICAL TIME SWITCH