2.5 Communication problem 

Inverter reports ​communication problem 
Battery-Box System State under Home shows ​STANDBY​ / ​IDLE 
Current Alarm: ​InverterCommError 

 

No. 

Name 

Description 

20 

Jumper 

See short instructions - please check: 
SMA: only  jumper  JP1 
KOSTAL: only jumper JP2 
FRONIUS: leave both jumpers (except for variant 2, see quick guide) 
GOODWE: leave both jumpers connected 

21 

Grounding 

Connected Battery-Box directly to the ground-bus of the house. Only with a correct 
grounding of the battery, a trouble-free and secure data transmission can be 
guaranteed. ​The battery must not be earthed via the inverter! Otherwise, 
communication problems are possible. Correct grounding is absolutely 
necessary!
 

22 

Communication cable 

 Replace the communication cable (min. CAT5!) 

23 

Use other communication 
port (J5 instead of J2) 

The BCU has two identical communication ports, labeled J2 and J5. The short 
guide show the wiring at J2. If there are any communication problems, try to 
connect the PINs to J5 instead. 

24 

Disconnect from the 
network 

Please check the local network  and  completely disconnect the system from the 
network in order to exclude communication interference caused by switches or 
WLAN repeaters (multicasting). 

25 

Restart the entire system 

Generally: 
- Switch off: Battery off >  Inverter off 
- wait at least 10 minutes! 
- Switch on: inverter on > battery on 
 
Kostal (the order is important): 
- unplug Ethernet cable from inverter 
- turn off the system: battery off > inverter DC switch off > AC off > unplug PV 
strings  
- wait at least 10 minutes 
- turn on system: plug in PV strings > AC on > inverter DC switch on > battery on 
- connect Ethernet cable once system is running again 

 

2.6 Current Alarm: BatteryDiff 

Error probably caused by  a faulty battery extension. 

No. 

Name 

Description 

26 

Battery recently 
extended? 
(new modules added) 

If the battery system has recently been extended: 
Remove the new modules from the system and follow the instruction on how to 
correctly extend the system (see extension manual) 
If no module extension has taken place and all modules have been installed at the 
same time, please contact EFT-Systems. Please make a screenshot of the section 
RUN Data​ on the web interface. 

 

 
 

5

 

Содержание BYD Battery-Box H10.2

Страница 1: ...tery Box HV are only allowed by professional and qualified electricians This manual is a shortened assistance for the installation of the Battery Box High Voltage and does not replace the original manual which can be found on www eft systems de or www byd com The installation must be carried out by a trained and qualified electrician Attention High Voltage Improper handling can cause danger and da...

Страница 2: ...roblem 5 2 6 Current Alarm BatteryDiff 5 2 7 Current Alarm UT OT e g Cell_UT SysTemp 6 2 8 Current Alarm Cell_UV1 Cell_UV2 Cell_UV3 6 2 9 Current Alarm DCBusFault 6 2 10 Voltage measurement 7 2 11 Visual Check 8 2 12 Identifying a faulty module Variant 1 8 2 13 Identifying a faulty module Variant 2 9 3 SERVICE TASKS 10 3 1 BCU replacement 10 3 2 Module Replacement 10 3 3 Charging with external HV ...

Страница 3: ...necessary 5 Installation in the Web Interface Installation Config Number of Modules Inverter Manufacturer Update install the latest released software www eft systems de 6 State of charge SOC When installed for the first time the battery will show a predefined SOC of 19 This does not correspond to the actual SOC and the battery corrects th eSOC at the first full charge or discharge The actual SOC o...

Страница 4: ...ment Please measure the voltage as shown in step 2 10 15 Check the individual modules variant 2 S ee step 2 13 2 3 Current Alarm BatteryCommErr Error probably caused by a communication failure between two modules or within a module No Name Description 16 Visual check See step 2 11 17 Check the individual modules variant 2 See step 2 12 2 4 Current Alarm MonitorCommErr Error probably caused by the ...

Страница 5: ...5 instead 24 Disconnect from the network Please check the local network and completely disconnect the system from the network in order to exclude communication interference caused by switches or WLAN repeaters multicasting 25 Restart the entire system Generally Switch off Battery off Inverter off wait at least 10 minutes Switch on inverter on battery on Kostal the order is important unplug Etherne...

Страница 6: ...sary Please go through the above steps especially check communication install updates restart the entire system If not recharge by inverter is not possible a charger may be required Switch off the battery and contact EFT Systems screenshots 30 UV2 If the battery is not being charged by the inverter immediately after restarting then switch off the battery after a few minutes and contact EFT Systems...

Страница 7: ...multiplying the number of modules by 50V Nominal system voltage should therefore be in the range 200V 450V If the measured voltage deviates significantly from the nominal value please check the electrical voltage at the individual modules as shown below Positive Negative Measurement 7 ...

Страница 8: ...es are logged in the History Alarm If an error is displayed in the Current Alarm or History Alarm then Sub1 shows which module is affected Please note The module number has nothing to do with the stacking order The module numbering is based on the production date and the oldest module has the number 1 The corresponding serial number can be obtained in RUN Data if you select the module number there...

Страница 9: ...s OK when battery is on Air Switch up and WIFI available no errors are shown Web Interface Current Alarm Otherwise the battery status is NOT OK OK Add one module at a time adjust module number in web interface and check again If battery status turns to NOT OK then the defect module is identified to be the one that has been added newly NOT OK The defect module is probably one of the 3 modules in th...

Страница 10: ...ut into operation not charged discharged the new module can easily be added Otherwise it is basically a module extension In this case please add the new module to the system only when the system has a SOC between 30 and 40 see extension manual 3 3 Charging with external HV charger You will receive a charger from us eg because of the message Cell_UV Each module should be individually connected to t...

Страница 11: ...ion B Photo of the BCU Complete BCU inside C Photos of Communication port PIN in the BCU and inverter In the BCU detail photo and on the inverter D D1 D2 D3 D4 D5 Screenshots of the web interface Device Information Installation Config Current Alarm History Alarm Run Data On the web interface E Serial number of the faulty module Note only necessary if a faulty module was found On top of the module ...

Отзывы: