EFI Titan 75LC Скачать руководство пользователя страница 1

© 2001 EFI Electronics Corporation   All Rights Reserved

1

8224-0005C    11/01

The 75LC Surge Protective Device (SPD) offers surge suppression and
noise filtration for any micro-processor based product, PLC’s, Motion
Control, OEM or any critical industrial load.  The SPD can be installed on
the incoming power source (20 amps or less).

INTRODUCTION

INSTALLATION

Titan 75LC 

Transient Voltage Surge
Suppressor (TVSS)

Instruction Bulletin

CLICK

3

2

2

2

1

1

1

CLICK

Figure 1: DIN Rail Mounting and Removing,

Flange Mounting

NOTE: (4) Mounting Feet are included for Flange Mounting 
applications.

CAUTION

HAZARD OF EQUIPMENT DAMAGE.

• Megger

®

or hi-potential tests will damage this surge protective

device. Turn off all power supplying the equipment and isolate the
surge protective device before testing.

• Not for use on ungrounded systems.

Failure to follow these precautions can result in equipment
damage.

DANGER

HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION.

• This equipment must be installed and serviced only by qualified

electrical personnel in accordance with National and Local Electrical
Codes. 

• Turn off all power supplying this equipment before working on or

inside equipment. 

• Always use a properly rated voltage sensing device to confirm power

is off. 

• Replace all devices, doors, and covers before turning on power to

this equipment. 

• Do not apply petroleum-based products to non-metallic parts.

Failure to follow these instructions will result in death or serious
injury. 

Отзывы: