Effekta MH RM 6000 Скачать руководство пользователя страница 1

 UPS 

Uninterruptible Power Supply 

MH RM 6000 

 

 

 

Manual 

Item no.:   ACX11MHR6K000000 

 

August 10

 

Содержание MH RM 6000

Страница 1: ...UPS Uninterruptible Power Supply MH RM 6000 Manual Item no ACX11MHR6K000000 August 10...

Страница 2: ...orage of the UPS 19 7 2 Unpacking of the UPS 19 8 Installation and connection of the UPS 20 8 1 Choice of the fitting position 20 8 2 Connection of the UPS 21 8 3 Communicational connection of the UPS...

Страница 3: ...11 Software 43 12 Maintenance and service 44 12 1 Measurement of the autonomy time 44 12 2 Exchange of the batteries 44 12 3 Service protocol 46 12 4 Service Hotline 47 12 5 Maintenance and service c...

Страница 4: ...Indicates additional information and tips Recyclable Indicates units which are liable to the WEEE waste elecal and electronic equipment directive Indicates units or parts which must be disposed Never...

Страница 5: ...uthorized interventions maloperation other devices or accessory wrong installation or other modifications which have not been authorized by us In case of misusing the instructions which were attached...

Страница 6: ...of other parties due to loss or damage Loss or damage of the records data or the costs of replacement of this data Economic consequential damages including lost benefits or economizations or accompany...

Страница 7: ...PS disposes of an intern energy source battery There can be voltage on the terminal output if the battery should be switched on even if there is no AC Ensure that the AC output is correctly grounded D...

Страница 8: ...e can be sparks smoke or gas During the transport you have to ensure that the UPS is switched off The UPS is equipped with a maintenance and bypass switch Pay attention to the application for the chan...

Страница 9: ...which heat excessively Ensure that the air slots of the units and the air circulation are not blocked 3 4 Connection The UPS just has to be connected to a earth contact socket or in case of terminal a...

Страница 10: ...y Dagers as to stumble to squeeze etc have to be avoided 3 5 Operation During the operation of the UPS the feeder never has to be uncoupled otherwise the protective grounding of the UPS and of the con...

Страница 11: ...Never throw batteries into domestic waste Follow the local directives of disposing 3 7 Maintenance service and errors Attention risk of electric shocks Even after cutting the current circuit the UPS s...

Страница 12: ...o errors omissions The UPS system is created to protect sensitive electric machines for example computers workstations electronic cases critical instruments telecommunication stations process control...

Страница 13: ...wing shows the particular modules and their interactions If the power failure goes longer than the autonomy time of the UPS it switches off automatically to avoid total discharge of the batteries When...

Страница 14: ...ding machine elements get instructions for the handling and get information concerning the connections of the UPS 6 1 Display and handling elements on the front side On the front side are all handling...

Страница 15: ...hin the still tolerated window 4 The green LED indicates that the voltage supply at the bypass input is normal 5 UPS switch on alert witch off 6 Return to the last page or change the installation of t...

Страница 16: ...de A blackout transfer has appeared at the output of the UPS Bypass input out of the tolerance UPS can not switch to bypass bypass fault in the eco mode Power supply out of the tolerance OFF UPS disco...

Страница 17: ...anual MH Series Page 17 of 50 Next page To log out in special functions Enter or confirm again LED power supply ok LED bypass supply ok UPS in redundancy mode UPS in eco working mode LED UPS fault Er0...

Страница 18: ...tial when attached Also when uncoupled dangerous voltage capacity in possible in the inside of the unit A RS232 port B Client s optional slot position 1 relays card C Client s optional slot position 2...

Страница 19: ...e continued every 2 months 7 2 Unpacking of the UPS Before installation check carefully the condition of the packaging and the external appearance Store the packaging material for future usage Remove...

Страница 20: ...t also with regard to the batteries 2 Always ensure that behind the UPS is enough place to connect the machines The underlay must have got a good carrying capacity 3 Respect the described fitting posi...

Страница 21: ...cht Illustriert die Anordnung der USV der Akkubank und des Bypassschalters optional 9 Do not install the UPS outside 8 2 Connection of the UPS Follow the following instructions and the fig 5 when conn...

Страница 22: ...pplied during the autonomy time 8 3 Communicational connection of the UPS A comfortable communicational connection is available for data exchange with the UPS The RS232 interface allows remote control...

Страница 23: ...ig 6 RS232 interface modulations Baud Rate 2400 bps Date length 8 Bits Stop bit 1 Bit Parity no For connection just use the cords which are described under the chapter accessories Fig 7 USV interne in...

Страница 24: ...relay interface Fig 8 DCE card relay card The pin configuration of the 10 pin terminal block Fig 9 pin configuration of the contact interface Pin Description 1 UPS bypass mode 2 Mains ok NO 3 Mains ok...

Страница 25: ...hapter Fehler Verweisquelle konnte nicht gefunden werden 8 3 2 2 SNMP cards SNMP WEB card Fig 10 SNMP WEB card With regard to the installation refer to the description attached to the card Fitting pos...

Страница 26: ...rface cards Follow those instructions for the installation of the hardware o Take the cover away of the slot o Move the chosen interface card into the slot o Fix the chosen interface card correctly 8...

Страница 27: ...n the ups and the battery 8 5 Connection order Connect the UPS with the supplying or bypass circuit but the circuits and the UPS have to be switched off during this procedure Connect your periphery wi...

Страница 28: ...e that voltage of supply conforms to the input voltage window of the UPS 4 Connect the main and bypass supply with the unit Switch the automatic breakers of the current distribution and of the UPS on...

Страница 29: ...nds in battery service If the self test is successful the drawing changes from E1 to F D indicates test on E1 indicates OK for the self test E2 indicates failure of the self test F indicates 220 V AC...

Страница 30: ...utton of the UPS again for about 3 seconds until the LCD display indicates drawing G until drawing H Now the UPS is in self mode The UPS can supply the output within 1 minute with energy and the LCD d...

Страница 31: ...g L UPS output voltage drawing M UPS output frequency drawing N UPS output charge drawing O UPS battery voltage drawing P UPS internal temperature I1 indicates voltage which comes from the bypass inpu...

Страница 32: ...output load O indicates battery voltage P indicates UPS internal temperature 9 4 UPS requirements and special functions 1 After the complete start of the UPS push the button to change the LCD display...

Страница 33: ...cy synchronization tolerance window drawing U inverter output voltage drawing V1 UPS service mode drawing W output voltage micro installation factor drawing X UPS id drawing Y no of the UPS in the par...

Страница 34: ...es that the frequency tolerance window is at 3Hz U indicates the inverter of the output voltage V1 indicates that the UPS is in normal mode Normalmodus V2 indicates that teh UPS is in eco mode komodus...

Страница 35: ...es that the UPS is the number 1 of the parallel systems 3 Push the button to scroll forward you can install special functions Those functions are buzzer on EIN drawing Q1 or buzzer off AUS drawing Q2...

Страница 36: ...200 V 208 V 220 V 230 V or 240 V The drawings V1 V2 V3 and V4 define the service modes of the UPS Following choices are possible online mode eco mode more economical and fixed frequency with 50Hz or...

Страница 37: ...buzzer resounds two times Switch the automatic breaker of the supplying input off The UPS is now unlocked but you should contact your local supplier to assure that the indicated error message is solv...

Страница 38: ...upply of the UPS and the automatic breaker of the bypass supply Now you can start maintenance It is necessary to start with step no 1 and then step no 2 If you forget step 1 the UPS will make a warnin...

Страница 39: ...1 Troubleshooting If failures occur during the UPS service you can check the following points 1 Is the connection of input and output correctly 2 Is the input voltage within the input tolerance window...

Страница 40: ...ve items which block the ventilated outputs 5 Ensure that the UPS is in normal service If it is in CVCF mode you have to switch off and start the UPS again 6 If the UPS is in CVCF mode the bypass inpu...

Страница 41: ...5 Batteries are low or have been bad during self test Er06 Short circuit at the output Er07 EPO mode Er08 DC BUS overload failed Er09 DC BUS under load failed Er10 Inverter over current Er11 UPS overh...

Страница 42: ...locks automatically into normal service mode if those failure codes for example occur Er06 Er07 Er13 Er14 Er23 Er24 Er26 Er28 Er29 If the bypass voltage is normal the UPS switches over to bypass suppl...

Страница 43: ...fekta com The following basic functions are supported by all software packages Capture and display of the mains condition of the UPS Display of the UPS output condition Capture and display of the load...

Страница 44: ...hod a is suited for the measurement of the real autonomy time whereas at the end of the autonomy time the user loads will be currentless Method b enables to detect the rested capacity after a defined...

Страница 45: ...to batteries Notice that there is still high voltage after disconnection for example voltage in the battery pack loading voltage of net capacitors Precaution regarding to electric shocks have to be re...

Страница 46: ...UPS MH RM 6000 Manual MH Series Page 46 of 50 12 3 Service protocol Please always inscribe hereunder every maintenance or service work on the UPS Date Activities Responsible...

Страница 47: ...5 Maintenance and service contracts EFFEKTA Regeltechnik GmbH offerst adequate maintenance and service contracts to guarantee the best liability and availability of the UPS Furthermore we can support...

Страница 48: ...s 150 immediately Efficiency factor AC AC normal up to 91 AC AC eco up to 98 DC input voltage 240 VDC Display status on LED LCD line mode backup mode eco mode bypass supply low battery bad disconnecte...

Страница 49: ...em number Software package PowerShut Plus Network compatible Shutdown and diagnosis software ex version 5 13 LAN PowerShut LAN RS232 connection Interface connection wire between UPS and PC M2505 Batte...

Страница 50: ...rements for the declaration of conformity The CE labeled UPS unit complies with the following harmonized standards and EU guidelines EU guideline 73 23 EEC for devices operating within a restricted vo...