8.Trouble shooting
It is very easy for the inverter’s maintenance. When you meet any problems, please refer to
the following trouble shooting first, please contact your local distributor if the problem can’t be
solved by yourself.
The following sheet lists some basic questions may encounter in the operation.
Alarm
Message
Failure description
Solution
F00-F03
AC voltage &
frequency
are too high or too low.
1.Pease check mains voltage whether it is
complied with local,safety standard
2.Please check the AC output line is properly
connected. Make sure its output voltage to see
if it is normal.
3.Disconnect PV input and restart the inverter
and check whether.
F04-F05
Bus voltage is too
high or too low.
1.Please check the setting of input mode
2.Disconnect PV input and restart the inverter
and check whether fault still exists.
F06
Bus voltage is
Unbalance
1. Please check the setting of input mode.
2.Disconnect PV input and restart the inverter
and check whether fault still exists.
3. The fault still exists after the restart. Please
contact the dealer
F07
Insulation
impedance Fault
1.Disconnect PV input and restart the inverter
and check whether fault still exists.
2.Please measure impedance of PV+/PV- to
ground whether is over than 500KΩ.
F08
Input Current High
1.Please check the setting of input mode.
2.Disconnect PV input and restart the inverter
and check whether fault still exists.
F09
Hardware Current
High
1. Disconnect PV input and restart the inverter
after few minutes and check whether fault still
exists.
F10
Inverter Current High
1.Disconnect PV input and restart the inverter
after few minutes and check whether fault still
exists.
F11
Inverter DC
Current high
1. Disconnect PV input and restart the inverter
after few minutes and check whether fault still
exists.
F12
Amb Temperature
Over
1.Disconnect PV input and cool down the
inverter then restart the inverter to see if it is
back to normal operation.
2.Please check environmental temperature
whether out of working temperature.
F13
Heatsink Temperature
High
1.Disconnect PV input and cool down the
inverter then restart the inverter to see if it is
back to normal operation.
2.Please check environmental temperature
whether out of working temperature.