Figure 4.12 Connect the DC Connectors to the Inverter
4.3.2 Connection of AC output
For all AC connections, 4-10mm² 105 XJ cable is required to be used. Please make sure the
resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's recommended to
use 10mm² cable.
WARNING:
There are"L "
,
"N''
,
'' PE'' symbols marked inside the connector, the Line
wire of grid must be connected to "L " terminal; the Neutral wire of grid must
be connected to "N" terminal; the Earth of grid must be connected to "PE" .
b. Insert the conductor into the suitable ferrule acc. to DIN 46228-4 and crimp the contact.
c. Unscrew the swivel nut from the threaded sleeve and thread the swivel nut and threaded
sleeve over the AC cable.