II.  PLUMBING HOOK-UP

1) The unit is supplied with ¾’’ NPT fittings (Figure 3), USE THESE. DO NOT USE

PIPE DOPE AND DO NOT SOLDER TO THE INLET OR OUTLET. 

2) Take care to ensure that the pipes are correctly aligned with the inlet and outlet bosses 

in order to avoid excessive stress on the heater body molding.
NOTE: When soldering pipe joints remove heater from the wall. Serious damage can occur

if any soldering is done while pipes are connected to the heater.
When tighten the fittings make sure to secure the fitting inside the heater to make 
a tight connection.
Run water through the supply pipe to remove all debris from the pipe before connecting
the heater. Failure to do so could cause damage to the flow switch.

3) Install isolating valves (full flow ball valve type) on both inlet and outlet pipes. This allows unit

to be isolated for maintenance purposes. (Fig. 1B)

4) When all plumbing is complete, fully check the system for water leaks at all the plumbing 

connections. If a leak is present take corrective action. Fully open both inlet and outlet
BALL VALVES.
Run all the hot water outlets fed by this heater one at a time, for a minute or two, until the water
flow  is continuous, free from “gulping” and from all visible air pockets.            

HOT OUTLET

¾’’ NPT

FITTING

DO NOT SOLDER

COLD INLET

¾’’ NPT

FITTING

DO NOT SOLDER

NOTE:

ALL MOUNTING AND PLUMBING MUST BE COMPLETE BEFORE YOU

PROCEED WITH ELECTRICAL HOOK-UP.

TEST THE INSTALLATION FOR LEAKS BEFORE CONNECTING THE

ELECTRICAL SUPPLY.         

9.962”

Figure 3

Содержание PA018208T2T

Страница 1: ...STALLER CONSUMER RESPONSIBILITIES PLEASE TAKE THE TIME TO READ NOT ONLY THIS MANUAL BUT ALSO THE WARRANTY CARD ENCLOSED WARRANTY OF THIS HEATER WILL DEPEND ON PROPER INSTALLATION AND OPERATION THE WARRANTY SHALL BE VOID IF THE DESIGN OR STRUCTURE OF THE WATER HEATER HAS BEEN ALTERED IN ANY WAY WHATSOEVER THE MANUFACTURER OF THIS WATER HEATER WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO...

Страница 2: ...CURRENT PROTECTIVE DEVICE SHALL BE 150 OF THE RATING OF THE PRODUCT DO NOT USE SPACE SAVING BREAKERS WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR CONSULT THE LOCAL ELECTRIC UTILITY FOR FURTHER INFORMATION FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY WA...

Страница 3: ...ixed to the wall using all four mounting holes of the backplate Use an appropriate fastener for the weight For the unit to be mounted against hollow walls we suggest using steel wall anchors with the correct grip range and 10 32 screws at a minimum NOTE The heater should be installed below the level of all hot water outlets serviced by this heater Otherwise install spring loaded check valves on bo...

Страница 4: ......

Страница 5: ...X309 277V 277V CONTROL BOARD PART EX284E 309 240V 208 240V PART EX309 284 277V 277V PART EX256 208V PART EX257B 277V PART EX255B 240V Replacement Elements PA018208T2T EX720 PA024208T2T EX560 PA018277T2T EX1280 PA024277T2T EX960 PA032277T2T EX720 PA028240T2T EX630 ...

Страница 6: ...cting the heater Failure to do so could cause damage to the flow switch 3 Install isolating valves full flow ball valve type on both inlet and outlet pipes This allows unit to be isolated for maintenance purposes Fig 1B 4 When all plumbing is complete fully check the system for water leaks at all the plumbing connections If a leak is present take corrective action Fully open both inlet and outlet ...

Страница 7: ...ed in the flange on the backplate Ensure to check national and local building codes The Rating of the branch circuit over current protective device shall be 150 of the rating of the unit see chart above per UL 499 18 4 The live wires should be connected to the slots in the terminal block marked L1 L2 and L3 The ground lead must be connected to the slot marked GND GROUND MUST BE BROUGHT TO THE GROU...

Страница 8: ...r in the system will be purged out Two the heater units will be pressurized at the supply pressure This will prevent the elements free from air pockets while energized 4 At this point you may energize the hot water heater Note Unit has 3 separate circuit breakers Once energized the Thermostatic control touch pad display on the front cover will illuminate This is where and when you will program you...

Страница 9: ...sistance of the heating element across the two threaded termination rods on top of the element The resistance reading should be roughly 6 0 ohms If the resistance is much greater than this value call Eemax for a replacement element 5 ECO TRIPPED High Limit Thermostat TURN OFF THE FOUR MAIN CIRCUIT BREAKERS Reset by pushing in red button on each heater module If the Eco was tripped it will re engag...

Отзывы: