Electrical Connection  

The electrical installation is based on the different Models. Unit must be installed 

to independent double pole breakers as per Model Specs below 

MODEL

 

REQUIRED 
BREAKER

 

MAX AMP 

DRAW

 

AWG Cable

 

HA008240 

1 x40AMP* 

33 

#8 

HA011240 

1 x50AMP* 

46 

#6 

HA013240 

1 x60AMP* 

54 

#6 

Check all wires to make sure they are securely fastened and tightened. Before 

turning the power on make sure the system has been purged as required in the 

plumbing section.  When the unit is powered up the GREEN LED indicator light will 

turn ON and then OFF.  

*Double Pole 

Содержание HA008240

Страница 1: ...Installation Manual HA008240 HA011240 HA013240 Tested and certified by the Water Quality Association against NSF ANSI 372 for lead free compliance ...

Страница 2: ...LOW ALL RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS FAILURE TO FOLLOW PROPER PROCEDURE IS HAZARDOUS IT CAN ALSO DAMAGE THE HEATER AND VOID THE WARRANTY TURN OFF ELECTRICAL SUPPLY MAIN AND WATER SUPPLY BEFORE ATTEMPTING ANY INSTALLATION DO NOT TURN ON ELECTRIC OR WATER SUPPLY UNTIL INSTALLATION IS PROPERLY COMPLETED DO NOT remove the heater cover open the unit or break the seal This could cause DEA...

Страница 3: ...1 Hot Water Outlet 2 Cold Water Inlet 3 Celsius Fahrenheit Conversion 4 Setting Temp Display 5 Power Knob Temp Controller 6 Wire 7 Copper Ring 8 Copper Nut Part Identification ...

Страница 4: ...line to the left hand side Plumbing Once both water lines are fastened and secured you must run water through the unit for at least 2 to 3 minutes to flush any air pockets purging in the lines It is recommended that all faucets showers etc be run Failure to follow this step can cause permanent damage to the unit This procedure MUST be performed before any electrical power is turned on ...

Страница 5: ...REQUIRED BREAKER MAX AMP DRAW AWG Cable HA008240 1 x40AMP 33 8 HA011240 1 x50AMP 46 6 HA013240 1 x60AMP 54 6 Check all wires to make sure they are securely fastened and tightened Before turning the power on make sure the system has been purged as required in the plumbing section When the unit is powered up the GREEN LED indicator light will turn ON and then OFF Double Pole ...

Страница 6: ...ay will change Temperature Control Turning it clock wise increases the temperature setting Turning it counter clockwise will decrease the temperature setting You can set or adjust your temperature at any time between 80 F 140 F 4 4 C 60 C The temperature can be changed to your desired setting The Temperature Indicator light will only stay on when there is hot water in use ...

Страница 7: ...1KW 240V 46 1 1 5 50 HA013240 13KW 240v 54 1 1 5 60 VERIFY ALL VOLTAGE AMPERAGE INFO LISTED BELOW WITH THE ACTUAL LABEL SPECIFICATIONS ON YOUR UNIT FOR ANY CHANGES OR VARIATIONS GAUGE AND BREAKER SIZE CAN VARY BASED ON A NUMBER OF FACTORS INCLUDING SUPPLIED VOLTAGE AND LENGTH OF CIRCUIT CHECK LOCAL REQUIREMENTS ...

Страница 8: ...Eemax Inc 400 Captain Neville Drive Waterbury CT 06705 TOLL FREE 800 543 6163 TELEPHONE 203 267 7890 FAX 203 267 7975 e mail info eemaxinc com www eemax com ...

Отзывы: