REQUIRED MAINTENANCE PROCEDURE
To Be Performed by Qualified Personnel
MONTHLY CHECKS
M1) Ensure main circuit breaker is on.
M2) Open outlet valve(s) to run water thru unit. Ensure that the
minimum flow rate to switch on your heater is met, for this
figure refer to the front cover of this manual.
M3) Check outlet temperature for desired setting.
QUARTERLY CHECKS
Q1) Turn off main circuit breaker.
Q2) Remove front cover from heater.
Q3) Inspection of heater bodies and distribution manifold for
water leaks.
Q4) Inspection of 12 fuses (50 amp each) Class G
Example: Eemax p/n EX198, Ferraz AG50 or Bussman SC50
Q5) Inspection of 12 heater elements (see page 10 for element ohms)
Q5) Inspection of coarse inlet filter screen is clear from any debris.
Q6) Turn on main circuit breaker
(note: unit has live electrical)
Q7) Carefully perform steps M1 thru M3 with cover removed, observe
each module for an indicator light.
Q8) Turn off circuit breaker
Q9) Install front cover, then turn on main circuit breaker.