Inwall 4 Input/Output Module

 

 
IO44C02KNX 
      

Product and Applications description 

 

The  product  is  dedicated  to  interfacing  free potential contacts 
through  the  4  input  channels,  for  example sensors, traditional 
buttons,  etc.  and  4  output  channels  at  low  voltage  for  drive 
signal  lamp  or  LED  for  example  for  synoptics panels used for 
monitoring the installation.  
 
The  device  is equipped with appropriate communication inter-
face with the bus type TP1 (twisted pair) KNX European stan-
dard, according CEI EN 50090. 

 

Application Program

Application Program

Application Program

Application Program    

 
See Eelectron product Database: “Eel_db01.VD3”  
 
Maximum number of group addresses: 

30

30

30

30

 

This is the maximum  number of different group addresses the 
device is able to memorize. 
 
Maximum number of associations: 

30

30

30

30

 

This  is  the  maximum    number  of  associations  between  com-
munication  objects  and  group  addresses the device is able to 
memorize. 
 

Caution

Caution

Caution

Caution

:  each  transmission  object  has  usually  associated  a 

single  group  address. If  you  want  to  associate  to  a  transmis-
sion  communication  object  other  addresses  in  addition  to  the 
first,  please  note that you can add a maximum of 5 group ad-
dresses of this kind for the whole device. 
 

Technical data

Technical data

Technical data

Technical data    

 

Power Supply: 

 

 

 

Via bus EIB/KNX cable 

  Voltage     

 

21..30V DC 

  Current Consumption EIB/KNX 

< 10mA 

 

Input

Input

Input

Input    

 

  Number: 4 free contacts 

  Maximum Lenght of Connecting Cable:          

 10m 

  Voltage Scanning: Vn – 3,3 V DC (internally Generated) 

 

Output

Output

Output

Output        

 

  Number:  4  outputs for drive led – Max 0,5 mA 

    
Control Elements

Control Elements

Control Elements

Control Elements    

 

  Red LED and button EIB/KNX for programming the physical 

address 

 

Connections 

 

  EIB/KNX  2 Terminals for connections bus with 0,8mmØ 

 

  Input 

4  connector cable to be wired with 24 AWG 

 

  Output 

4  connector cable to be wired with 24 AWG 

 

Electrical 

Electrical 

Electrical 

Electrical Pattern

Pattern

Pattern

Pattern    

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

Mechanical Data

Mechanical Data

Mechanical Data

Mechanical Data    

• Case: plastic  
• Protection class: II in accordance with EN 61140  
• Dimensions: (width x height. X depth.): 43 x 36 x 17 mm  
• Weight: approx. 30 g 
 
 
 

 

 

    

Electrical Safety  

 
• Degree of pollution (IEC 60664-1): 2  
• Degree of protection (EN 60529): IP 20  
• Protection class (according to IEC 1140): III  
• Overvoltage class (according to IEC 664-1): III  
• Bus: safety voltage SELV DC 24 V  
• Meets EN 50090 and IEC 664-1: 1992 

 
EMC Requirements  

 
Complied with EN 50081-1, EN 50082-2 and EN 50090-2.2 

 

Terms of use  

 
• According to EN 50090-2.2  
• Ambient temperature during operation: 0 °C + 45 °C  
• Storage temperature: - 20 °C + 55 °C   
• Relative humidity: max 90% 

    
Certification

Certification

Certification

Certification    

 
EIB/KNX certificate 

 

CE Mark 

 
According to EMC guideline and low voltage directive 

 
 
 

Indicators Position and Control Elements

Indicators Position and Control Elements

Indicators Position and Control Elements

Indicators Position and Control Elements    

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Wired Connectors: 

 

1. 

Black Common in/out 1 

2. 

White in 1 

3. 

Yellow out 1 

4. 

Black Common in/out 2 

5. 

Red in 2 

6. 

Orange out 2 

7. 

Black Common in/out 3 

8. 

Green in 3 

9. 

Blue out 3 

10.  Black Common in/out 4 
11.  Violet in 4 
12.  Grey out 4 
15.  Terminal Connection Bus (graft): 

-  negative pole Black 
+  positive pole Red 

 
Control Unit And Display: 

 

14.  ETS programming led 
13.  ETS programming switch 
 
 
 
 
 

 

 

Installation Instructions 

 
The device may be used for permanent indoor installations 
in dry locations within wall box mounts. 
 

WARNING 

  The device must not be connected to 230V cables 

  The prevailing safety rules must be heeded. 

  The device must be mounted and commissioned by an 

authorised installer. 

  The applicable safety and accident prevention regula-

tions must be observed. 

  The device must not be opened. Any faulty devices 

should be returned to manufacturer. 

  For planning and construction of electric installations, the 

relevant guidelines, regulations and standards of the re-
spective country are to be considered. 

 
 

Mounting and Wiring hints 

 
General Description 

The  device  configuration  (KNX  physical  address  assign-
ment) is done by pressing the programming push button (10) 
located  in  the  back  side  of  the  housing.  Please  take  care 
during  installation  to  leave  connection wires long enough in 
order to remove the device easily from the wall box for com-
missioning. 

 
Connecting bus cables

 

  Connect  each  single  KNX/EIB  bus  core  inside  the  termi-

nal block (11) observing bus polarity . 

  Slip  the  bus  connection  block  (11)  into  the  guide  slot 

placed  on  the  back  side  of  this  device  and  press  the 
block down to the stop. 

 
 
 
For further information please visit 

www.eelectron.com

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

eelectron spa 

Via Magenta 77/22  
I-20017 Rho (MI) - Italia  
Email: [email protected] 
Web: www.eelectron.com

 

 
 

1

2

3

4

5

6

7

8

9

10

11

12

 

 

 

 

 

 

 

 

 

 

 

 

KNX Interface 

IN1

OUT1

COM 1

OUT2

IN2

COM 2

OUT3

IN3

COM 3

OUT4

IN4

COM 4

KNX  BUS  

BLACK
WHITE
YELLOW

RED

BLACK

GREEN
BLUE

BLACK

ORANGE

BLACK

GREY

VIOLET

1

2

3
4

5
6

7

8
9

10

11

12

13

14

15