CTM City Tie Module Installation Sheet 

1

2

3

4

2

1

 

Description 

The CTM City Tie Module provides a single municipal box 
connection for activating a local energy type master box 
connected to a public fire alarm reporting system.  

Installation 

Install the CTM in accordance with NFPA 70 National Electrical 
Code. 

WARNING:

 This device will not operate without electrical 

power. As fires frequently cause power interruptions, we 
suggest you discuss further safeguards with your fire 
protection specialist. 

The CTM is shipped from the factory as an assembled unit; it 
contains no user-serviceable parts and should 

not 

be 

disassembled. 

For more information, refer to the technical reference manual 
listed inside the control panel door. 

To install the module: 

1.  Verify that all field wiring is free of opens, shorts, and 

ground faults. 

2.  Make all wiring connections as shown in the wiring 

diagram. See Figure 1. 

4.  Using the 4-24 × 1/2 in (13 mm) self-tapping screw 

provided, mount the wall plate to the module.  

5.  Using the two 6-32 × 1/2 in (13 mm) machine screws 

provided, mount the module to the electrical box. 

Wiring 

Wire the CTM to a dedicated notification appliance circuit 
(NAC) as in Figure 1 on page 2. Do not install other notification 
appliances on the same circuit.  

Specifications 

 
Voltage 

24 VDC nom. 

Current 
 Standby 
 Alarm 

 
20 mA 
300 mA, max. 

Ground fault impedance 

 

Wire size 

12 to 18 AWG (0.75 to 2.5 sq mm) 

Mounting 

North American 2-1/2 in (64 mm) deep  
1-gang box 

Municipal box connection 
 Wire 

resistance: 

 Trip 

current: 

 
26 

 

200 mA into a 14.5 

 coil 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

 
 

 