P-047550-0857  ISSUE 3 © 1998

FARMINGTON, CT  203-699-3000  FAX  860-677-7746

Installation Instructions for Remote Amplifiers

Catalog Series 5535

EDWARDS

Installation

Installation should be completed in accordance with applicable
local codes and the latest edition of either NFPA 70, National
Electrical Code, or CSA C22.1, Canadian Electrical Code.

Each 5535 Series Remote Amplifier may be mounted to any flat
surface or may be used as a freestanding unit mounted to a rigid
pipe.

NOTE: During installation, take care not to damage the

components on the printed circuit board.

1.

Mount Adaptatone (Figure 2).

a.

Remove (4) cover screws from the signal box and lift off
cover.

b.

Flat Surface Mounting.  Secure unit to mounting surface
at the (2) mounting holes in rear of box with furnished
O-rings and #10 X 1 1/2" (38 mm) screws (supplied).
For mounting to dry wall or concrete surfaces, use
furnished O-rings and suitable hardware (not supplied).

c.

Rigid Pipe Mounting.  Seal the (2) mounting holes in
rear of box with (2) furnished O-rings and #12 X 3/8"
(9.5 mm) long screws.

Remove the center knockout in lower wall of box and
mount box to a 1/2" (12.7 mm) conduit pipe using
suitable  connector (not supplied).

2.

Install wires through a knockout hole in the bottom of the
box when the signal is mounted to a  flat surface, or through
the pipe when the signal is freestanding.  In areas of high
electrical noise, use shielded audio cable.

Description and Operation

Edwards remote amplifiers are designed to accept tones, voice,
or music inputs from 5541 System control units or tones from
5540 Series Tone Generators.  The amplifiers convert the input
signals to 70V line output (up to 15 watts) to sound on speakers
in remote locations.  The remote amplifiers are UL listed and
CSA certified as audible signal appliances for general signaling
(non-fire alarm) use.

Mechanical Specifications

Weight ............................................................. 7 Pounds (3.2 kg)
Variable Ambient Temp. ............ -31F to +151F (-35C to +66C)

Electrical Specifications

Figure 1.  Dimensions

INPUT POWER

Typical Current

Catalog

Standby

Tone On

Number

Voltage

Current (A)

Current (A)

5535-N5

120V 60 Hz

.11

.31

120V 50 Hz

.30

.40

24V DC

.02

.60

5535-R5

240V 60 Hz

.053

.20

240V 50 Hz

.064

.25

24V DC

.018

.60