background image

© 2014 UTC Fire & Security Americas Corporation, Inc. 

1 / 4 

P/N 270495-

EN • REV 06 • ISS 10JUL14

 

 

Power Supplies  

Installation Sheet 

 

Description 

This installation sheet applies to the following models: 

  3-PPS/M(-230) Primary Power Supply 

  3-BPS/M(-230) Booster Power Supply 

  3-BBC/M(-230) Booster/Charger Supply  

3-PPS/M(-230) Primary Power Supply 

The 3-PPS/M(-230) Primary Power Supply provides the required 

power and related supervision functions for the control panel. The  

3-PPS/M(-230) comprises a heat sink assembly and a monitor module. 

The monitor module plugs into the rail, and the heat sink and the heat 

sink assembly mount onto the rail chassis. 
The 3-PPS/M(-230) provides filtered, regulated power to the rail 

chassis modules as well as 24 

VDC

 for operating ancillary equipment. 

AC power and battery connections are made to fixed terminals on the 

heat sink assembly, away from the panel’s power-limited wiring. 
The 3-PPS/M(-230) provides a dual rate constant current battery 

charger circuit with automatic temperature compensation. To prevent 

memory problems and total battery discharge, a battery monitor circuit 

supervises the standby batteries and disconnects them when they 

reach the low battery threshold. 
The 3-PPS/M(-230) checks the AC input source and automatically 

switches to battery power in the event of a brownout or loss of AC 

power. In the event of a failure of one or more booster power supplies, 

the 3-PPS/M(-230) determines its ability, along with the surviving 

booster supplies, to supply the load. If the load exceeds the ability of 

the primary and surviving booster supplies to meet the demand, the  

3-PPS/M(-230) automatically switches in the standby batteries. The  

3-PPS/M(-230) also switches in the standby batteries if an overload 

causes the heat sink temperature to reach a high level. 
The power supply monitor module provides the interface between the 

3-PPS/M(-230) and the panel, making the required data and power 

connections to and from the rail chassis. The monitor module requires 

one rail space and is secured to the assembly using snap rivet 

fasteners. The monitor module has a hinged front panel for mounting 

displays or a blank protective faceplate. 

3-BPS/M(-230) Booster Power Supply and 3-BBC/M(-230) 

Booster/Charger Supply 

The 3-BPS/M(-230) and 3-BBC/M(-230) booster power supplies are 

used to provide additional power over and above that of the  

3-PPS/M(-230). Each model is composed of a heat sink assembly and 

a monitor module. The monitor module plugs into the rail and the heat 

sink assembly mounts onto the rail chassis.  

Depending on the size of the cabinet, up to three booster power 

supplies can be added to make a total of 28 A available for both 

internal and external applications. Each booster supply provides 

filtered, regulated power to the rail chassis modules as well as 24 

VDC

 

for operating ancillary equipment. 
A 3-BPS/M(-230) supply can share a common set of standby batteries 

with the 3-PPS/M(-230) or 3-BBC/M(-230). Each 3-BPS/M(-230) 

supervises its own battery connection but does not have any battery 

charging capability. The 3-BBC/M(-230) is capable of charging standby 

batteries. 
Each booster supply shares the panel's 24 

VDC

 electrical load with the 

3-PPS/M(-230). In the event of a booster power supply failure, a 

trouble is annunciated, and the panel load is distributed among the 

remaining operational power sources. Should the load ever exceed the 

ability of the operable power sources to supply the power, as in the 

event of an alarm, the system automatically switches to standby 

batteries.  
The booster supply monitor module provides the interface between the 

booster power supply and the panel, making the required data and 

power connections to and from the rail chassis. The monitor module 

requires one rail space and is secured to the assembly using snap 

rivet fasteners. The monitor module has a hinged front panel for 

mounting displays or a blank protective faceplate. 

Installation 

Installing a heat sink assembly 

Heat sink assemblies are installed on the rail chassis behind the rail 

module connectors. Refer to 

Figure 1. 

To install a heat sink assembly: 

1.  Attach the heat sink assembly to the four threaded mounting studs 

on the rail chassis using lock nuts provided in the hardware kit. 

2.  Secure the bottom edge of the heat sink assembly to the threaded 

standoffs on the rail chassis using screws provided in the 

hardware kit. 

3.  Secure the top edge of the heat sink assembly to the rail chassis 

using the two threaded standoffs provided in the hardware kit. 

4.  Attach the AC terminal block cover to the threaded standoffs using 

two #

6

-32 x 1/2 pan head screws. 

Notes 

 

  Always mount the heat sink assembly for the primary power supply 

onto the left mounting space of the rail chassis in which the central 

processor module is installed. 

  Booster supplies, if installed, can be mounted on any rail chassis, 

but no more than three booster supplies may be installed in the 

same enclosure. 

TB1

P3

TB2

P

2

+BATTERY-

MON

TEMP

TB

1

AUXILIARY POWER

1

2

Heat sink

assembly

Monitor

module