background image

Installation Sheet 

18AUG05 

 P/N: 3100686 REV: 2.0 

SuperDuct Four-Wire Smoke Sensor (RJ-45 version) 

 

1 / 3 

SuperDuct 

Four-Wire Smoke Sensor (RJ-45 version) 

 

Product description 

 

The SuperDuct four-wire smoke sensor coupled with a compatible 
controller make up a SuperDuct four-wire duct smoke detector. The 
sensor sends an alarm signal to the controller when smoke is detected 
in the HVAC system. Upon receipt of the alarm signal, the controller 
takes the appropriate actions to provide early warning of the impending 
fire and prevent smoke from circulating throughout the building. 
Sensors can be installed on the supply side and the return side of the 
HVAC system. 

WARNING: 

SuperDuct duct smoke detectors are not intended as a 

substitute for open area protection. 

The sensor comprises a plastic housing, a printed circuit board, a clear 
plastic cover, and an exhaust tube. The clear plastic cover permits 
visual inspections without having to disassemble the sensor. The cover 
attaches to the sensor housing using four captive screws and forms an 
airtight chamber around the sensing electronics. 

A sampling tube is required to introduce air into the sensor. The 
sampling tube is ordered separately and varies in length depending on 
the width of the HVAC duct. 

This document provides installation instructions for the following 
SuperDuct four-wire smoke sensors: 
 

Model Description 

TSD-SJ, ESD-SJ, 
SD-SJ 

Four-wire smoke sensor with RJ-45 modular 
connector  

TSD-SJG 

Four-wire smoke sensor with RJ-45 
modular connector and cover gasket 

TSD-SJCO2 

Four-wire smoke sensor with RJ-45 
modular connector and TSD-CO2 module 

Note: 

The TSD-CO2 module has not been performance evaluated to 

UL 2075 or approved by ULC. 

Related documents 

In addition to this document, information about controller installation 
and duct smoke detector testing and maintenance can be found in the 
following: 

• 

SuperDuct Four-Wire Controller (RJ-45 version) Installation Sheet 

(P/N 3100687) 

• 

SuperDuct 24V Four-Wire Controller (RJ-45 version) Installation 
Sheet 

(P/N 3100962) 

• 

SuperDuct Four-Wire Duct Smoke Detector Technical Bulletin 

(P/N 3100685) 

Specifications 

Dimensions: 8.70 x 5.45 x 1.90 inches 
Smoke detection method: Photoelectric (light scattering principle) 
Air velocity rating: 100 to 4,000 ft/min 
Air pressure differential: 0.005 to 1.00 inches of water 
Sensitivity: 0.67 to 2.46 %obscuration/ft 
Reset time: 2 seconds, max. 
Power up time: 8 seconds, max. 
Alarm test response time: 5 to 7 seconds 
LED indicators: Alarm (red), Trouble (yellow), Dirty (yellow), Power 

(green) 

Current requirements: Included in controller specifications 
Operating environment 

Temperature: -20 to 70 

°

C (-4 to 158 

°

F) 

Temperature with TSD-CO2 module installed: 0 to 55 

°

(32 to 131 

°

F) 

Humidity: 10 to 93%, RH noncondensing at 68 to 72 

°

C (154.4 to 

161.6

°

F) 

Sensor limitations 

The sensor will not operate unless connected to a SuperDuct four-wire 
controller fitted with RJ-45 modular jacks. 

The sensor will not sense smoke unless its cover is properly installed 
and air is moving through the ventilation system. 

The sensor must be installed according to these instructions and in 
accordance with all applicable national and local codes as determined 
by the local authority having jurisdiction. 

The sensor must be operated within the specified electrical and 
environmental limits. 

Installation guidelines 

Install the sensor on a flat section of HVAC duct between six and ten 
duct widths from any bends or obstructions and not more than 15 ft 
from its controller. 

Install supply-side sensors at a point downstream from the supply fan 
and after the air filter. 

Install return-side sensors at a point before the return air stream is 
diluted by outside air. 

Sampling tubes must extend at least two-thirds across the width of the 
duct. Sampling tubes longer than 36 inches must be supported at both 
ends. 

Installation instructions 

Please read these instructions thoroughly before installing. In addition 
to this document, important information can be found in Technical 
Bulletin P/N 3100685.

 

Step 1: Verify the duct air velocity 

Drill a small hole at the point where the sensor is being installed. Using 
the SD-VTK Air Velocity Test Kit and a suitable air velocity meter, 
verify that the air velocity in the HVAC duct falls within the specified 
operating range of the sensor and note which direction the air flows.  

If the air velocity does not fall within the specified range, relocate the 
sensor and seal all holes in the HVAC duct. 

Отзывы: