background image

© 2013 UTC Fire & Security. All rights reserved. 

1 / 2 

P/N 3101206 • REV 02 • REB 28JAN13 

 

E-SDPCB Duct Smoke Detector PCB 
Replacement Kit Installation Sheet 

Description 

The duct smoke detector PCB replacement kit is used to repair 
E-PDD duct smoke detectors in the field. The kit contains a 
printed circuit board and two sensing chamber gaskets. 

Installation 

WARNING: 

Before replacing the duct smoke detector’s printed 

circuit board assembly, notify the proper authorities that the fire 
alarm system is undergoing maintenance and take steps to 
prevent the control panel from responding to a false alarm. 

 

Caution: 

This product contains components that are sensitive 

to static electricity. Use approved handling precautions to 
prevent damage from electrostatic discharge. 

To replace the detector printed circuit board: 

1.  Remove and retain the four screws securing the detector 

cover, then remove the cover. 

2.  Identify the wire locations at the terminal blocks, then 

disconnect wires. 

3.  Note the device address set on the rotary switches, then 

set the same device address on the replacement printed 
circuit board. 

4.  Note the position of the JP3 jumper, and then set the 

same JP3 jumper setting on the replacement printed 
circuit board. 

5.  Remove and retain the four screws securing the printed 

circuit board to the detector housing, and then remove the 
printed circuit board. 

6.  Replace the sensing chamber gasket on the detector 

housing with a new gasket from the kit.  

7.  Secure the replacement printed circuit board to the 

detector housing using the four screws previously 
removed. 

8.  Connect the terminal block wiring at the locations marked 

during removal. 

9.  Replace the sensing chamber gasket on the detector 

cover with a new gasket from the kit. 

10.  Secure the detector cover to the detector housing using 

the four screws previously removed. 

11.  Test the detector in accordance with “Testing”. 

Figure 1: Replacement diagram 

Detector housing

Sensing
chamber
gasket

Rotary
switch

HVAC duct

Detector cover

(rear view)

Sensing chamber gasket

PCB assembly

JP3 jumper

4 x 1/4 48-2

plastite screw

(4X)

Airflow

 

Testing 

After replacing the duct smoke detector printed circuit board, 
the unit must be tested to ensure it is operating correctly before 
leaving the job site. For details, refer to Technical Bulletin  
P/N 3101212. 

 
 