Description 

The horn/strobes are high quality signals intended for use in 
general signaling applications. The strobes flash at 1 fps 
across their full operating voltage range. 

It is recommended that these products be installed in 
accordance with the requirements in the latest edition of 
national and local electrical codes. 

See Table 2 and Figure 1 for specifications. 

Table 1: Electronic horn/strobes 

Catalog number 

Description 

867STR(*)-** 

Horn/Strobe, Surface Mount Indoor, Gray 

868STR(*)-** 

Horn/Strobe, Surface Mount Outdoor, Gray 

869STR(*)-** 

Horn/Strobe, Flush or Panel Mount Indoor, Gray 

Insert lens color: C = Clear, R = Red, G = Green, B = Blue or A = 

Amber. 
** 

The horns are available in two voltages. Insert suffix as required: 

N5 = 120V AC, AQ = 24V AC/DC

 

Installation 

WARNINGS 

• 

To reduce the risk of shock, do not connect AC or battery 
power to the horn until directed in these instructions.  

• 

To reduce the risk of shock, do not tamper with this device 
when the signal circuit is energized. Disconnect all power 
and wait 5 minutes for stored energy to dissipate before 
handling. 

1.  Select a mounting method as detailed in Figure 1 and 

install the electrical box using suitable hardware. 

a.  For outdoor applications, install the weatherproof box 

using four #10 x 1 1/4" (32 mm) screws and caplugs 
provided in the enclosed parts bag. Carefully adhere 
the gasket, part number P-007549-0082 (provided in 
the enclosed parts bag) to the box as shown in 
Figure 1. 

 

Notes

  

• 

Be sure hook flange is facing outward as shown in 
Figure 1. 

• 

The designation "TOP" on boxes denotes orientation 
of box after installation. 

2.  Attach mounting plate using two #8-32 screws provided 

with the surface box or four #8-32 screws provided with 
weatherproof box. The flush box uses two #8-32 screws 
(not provided). 

3.  Bring signaling circuit field wiring into electrical box. 

4.  Connect signaling circuit field wires to terminals on 

horn/strobe 

assembly (

Figure 2

 through 

Figure 4

). 

5.  Ground in accordance with national and local electrical 

codes. A green ground screw is provided with both the 
indoor and outdoor surface boxes. 

6.  Mount the horn/strobe assembly on the mounting plate 

(Figure 1). 

a.  The inside of the top of the grille has hinges that pass 

through cutouts and engage with tabs on the 
mounting plate. With the bottom of the grille lifted out 
slightly, place the grille over the mounting plate so 
that the hinges of the grille are in the mounting 
cutouts. 

b.  Properly seat the grille by pressing the bottom in. 
c.  Fasten the bottom of the grille to the mounting plate 

by installing the captive combination drive screw. 

7.  Apply power and activate the horn/strobe unit to verify that 

it is operating properly. 

Maintenance 

Caution: 

Should the unit fail to operate properly, do not 

attempt repair. Contact the supplier for replacement. 

Perform a visual inspection and an operational test twice a 
year. 

 