MMU-16LE
SmartMonitor
Operations Manual
Eberle Design Inc.
Page 42
Section 9
Timing Functions
Conflict
No Fault ...................................................................................... less than 200 msec
Fault ....................................................................................... greater than 450 msec
Typical ........................................................................................................ 350 msec
Red Fail
No Fault ...................................................................................... less than 700 msec
Fault ..................................................................................... greater than 1000 msec
Typical ........................................................................................................ 850 msec
Controller Voltage Monitor (CVM)
No Fault ...................................................................................... less than 125 msec
Fault ....................................................................................... greater than 175 msec
Typical ........................................................................................................ 150 msec
+24Vdc Monitor
No Fault ...................................................................................... less than 125 msec
Fault ....................................................................................... greater than 175 msec
Typical ........................................................................................................ 150 msec
Local Flash Status
No Fault ...................................................................................... less than 125 msec
Fault ....................................................................................... greater than 175 msec
Typical ........................................................................................................ 150 msec
Clearance Fail
No Fault ............................................................................... greater than 2.8 second
Fault .......................................................................................... less than 2.6 second
Typical ...................................................................................... less than 2.7 second
Port 1 Fail
Typical ........................................................................................................ 300 msec
Field Check Fail
Typical ...................................................................................................... 1000 msec
Dual Indication
No Fault ...................................................................................... less than 200 msec
Fault ....................................................................................... greater than 500 msec
Typical ........................................................................................................ 400 msec
Dual Indication (Pedestrian Channels)
No Fault ...................................................................................... less than 700 msec
Fault ..................................................................................... greater than 1000 msec
Typical ........................................................................................................ 850 msec
MMU Power Fail
Respond ................................................................................ greater than 500 msec
No Response .............................................................................. less than 450 msec
Minimum Flash ............................................................................. 6 to 16, +
_
Start Delay ........................................................................................ 2.0
1 second
+
_0.5 second