background image

CMUip-2212 Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 1 

Section 1  

GENERAL 

1.1 OVERVIEW 

The model CMUip-2212 Cabinet Monitor Unit (CMUip-2212) is the principle part of the ATC 

Traffic Control Cabinet Monitoring System. It is resident in the Output  Assembly and 

communicates with the High Density Switch Packs (HDSP)  located in each Output 

Assembly via Serial Bus #3. The role of the CMUip-2212  is to query various cabinet 

conditions and, if the application requires action, the CMUip-2212 will transfer control from 

the Advanced Traffic Controller (ATC) to a flashing control mode. Applications include the 

detection of, and response to, improper and conflicting signals and improper operating 

voltages in a cabinet assembly caused by malfunctions of the (ATC), load switches, or miss 

wiring of the cabinet. 
The communications between the ATC and the CMUip-2212  via Serial Bus #1 plays an 

integral role in ensuring safe and proper operation of the cabinet equipment as well as 

providing important diagnostic functions used for trouble shooting malfunctioning 

equipment. 

 

1.2 CHANNEL CONFIGURATION 

The CMUip-2212 can be configured to monitor up to 32 physical load switch channels of 

three inputs per channel. Each channel is comprised of a Red / Dont Walk input, a Yellow 

input, and a Green / Walk input.  
When populated with fourteen or less HDSPs, an additional four virtual channels can be 

programmed in the CMUip-2212 to provide a total of 32 logical channels. 

1.3 HIGH DENSITY SWITCH PACK (HDSP) 

The  HDSP-FU  (

iPack

®

  2202)  provides the CMUip-2212  with voltage and current 

measurements from each installed Output Assembly. Each  HDSP  has the capability to 

measure and report field terminal voltages  and  load currents  for  two  channels of three 

outputs per channel. Each HDSP is configured by its Output Assembly address. For further 

 

Service

Assembly

Output Assembly

ATC

CMU

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

F

U

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

S

P

H

D

F

U

SIU

SIU

Serial Bus #3

Serial Bus #1

Serial Bus #1

ADU

Содержание CMUip-2212 Series

Страница 1: ...TOR UNIT Firmware Version 2 0 vXX20 Issue J PCB REVISION MAY 2019 pn 888 2212 001 CMUip 2212 ATCC Cabinet Monitor Unit Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4 5 OR HIGHE...

Страница 2: ...ETARY TECHNICAL INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2019 EDI U S Pat No 7 246 037 Can...

Страница 3: ...ance Monitor 6 2 8 Yellow Plus Red Clearance Monitor 7 2 9 Local Flash Status 7 2 9 1 Local Flash Status Recovery 7 2 10 Circuit Breaker Trip Status 7 2 11 Flasher Unit Output Failed Alarm 7 2 12 CMU...

Страница 4: ...s 1 Address Inputs 16 3 7 Serial Bus 1 Disable input 17 3 8 CMUip 2212 Temperature 17 Section 4 FRONT PANEL DESCRIPTION 18 4 1 Indicators 18 4 1 1 Power Indicator 18 4 1 2 48VDC FAIL Indicator 18 4 1...

Страница 5: ...6 1 1 CMUip 2212 HV CMUip 2212 VHV Pin List 25 6 1 2 CMUip 2212 LV Pin List 25 6 2 CMUip 2212 Ethernet LAN Port 26 6 2 1 Ethernet LAN Cable 26...

Страница 6: ...roper operation of the cabinet equipment as well as providing important diagnostic functions used for trouble shooting malfunctioning equipment 1 2 CHANNEL CONFIGURATION The CMUip 2212 can be configur...

Страница 7: ...CMUip 2212 provides limited operational status Detailed status is obtained through the front panel Ethernet port CMUip 2212 using Eberle Design ECcom Signal Monitor Communications software running on...

Страница 8: ...is data allows the CMUip 2212 to better respond to and diagnose fault situations 1 7 1 SERIAL BUS 1 MESSAGE TYPES The CMUip 2212 is compatible with the following message types Type 60 Module Identific...

Страница 9: ...Reset Button or EXTERNAL RESET TEST input or a CMUip 2212 Power Fail will reset a LATCHED RESETTABLE FAILED STATE ACTION LFSA R A NONLATCHED FAILED STATE ACTION NFSA will be reset if the fault condit...

Страница 10: ...ause a LFSA 2 3 SERIAL BUS MONITOR The CMUip 2212 communicates with both Serial Bus SB 1 and 3 In SB 1 the CMUip 2212 is a Secondary device polled by the ATC Primary device On SB 1 the CMUip 2212 will...

Страница 11: ...5 and 16 when Virtual channels are used Lack of Signal Input monitoring will be disabled for all channels when the MC COIL STATUS input is not active There is programming in the Datakey to disable Lac...

Страница 12: ...y Unit ADU will display the active field signals This can be helpful to verify that flash mode is active on all outputs appropriately Note that a short time delay will be introduced to the ADU display...

Страница 13: ...e high the CMUip 2212 will begin timing the programmed Minimum Flash Interval During the Minimum Flash Interval the CMUip 2212 will be in NFSA 2 12 4 POWER UP Following initial application of MAINS vo...

Страница 14: ...triggered the CMUip 2212 to the fault mode and the CMUip 2212 indicates that there is no Field Check Status the ATC or ATC programming is the most likely cause The lack of Field Check Status indicate...

Страница 15: ...or pulsing in nature The RMS signal detection algorithm is designed to filter out short term transients commonly found on the electrical service and provide noise immunity against false signal detect...

Страница 16: ...PROTECTED TURN CHANNEL The Protected Turn Channel of the FYA channel pair is composed of the solid Green arrow Ga indication of the FYA Signal Output Group 2 16 1 2 PERMISSIVE TURN CHANNEL The Permiss...

Страница 17: ...ogramming of the Protected Turn channel Green arrow of the pair 2 16 2 1 2 PERMISSIVE YELLOW CHANGE INTERVAL CONFLICT During the Yellow change interval of the Permissive Turn channel flashing Yellow a...

Страница 18: ...rmissive flashing Yellow arrow This allows the CU to sequence from the Permissive Left turn channel directly to the Protected Left Turn channel without a solid Yellow arrow clearance interval 2 16 3 R...

Страница 19: ...ough channel is still showing a green ball When the FYA Yellow Trap Conflict condition is detected the CMUip 2212 will enter the fault mode transfer the OUTPUT relay contacts to the Fault position and...

Страница 20: ...ill be sensed active when the load current exceeds the programmed Channel LOS Current Sense Threshold programmed for that channel in the Datakey A channel will not be sensed active when the load curre...

Страница 21: ...be considered active see Section 5 1 when the door is open These inputs will not be considered active when the door is closed The CMUip 2212 will report the state of these inputs in the Type 209 195 f...

Страница 22: ...When the SERIAL BUS 1 DISABLE input is connected to VDC GROUND True The CMUip 2212 will not communicate on Serial Bus 1 or set a FSA condition if communications from the ATC is not present See sectio...

Страница 23: ...d The 48VDC 24VDC FAIL and 12VDC FAIL will pulse when either the POWERDOWN or NRESET input is False low See section 2 12 2 4 1 4 12VDC FAIL INDICATOR A red 12VDC FAIL indicator will illuminate when th...

Страница 24: ...ator will illuminate when the CMUip 2212 is in FSA as a result of a Serial Bus 3 fault See section 2 3 2 4 1 14 DIAGNOSTIC INDICATOR A red DIAGNOSTIC indicator will illuminate when the CMUip 2212 is i...

Страница 25: ...power is applied to the CMU 2212 the CMUip 2212 will continue to use the parameters from the removed Datakey until Reset is applied a new Datakey is installed or a power up cycle occurs If a CMUip 22...

Страница 26: ...ss than 77 Vrms DC Control Monitors Local Flash Status MC Coil Status FTR Coil Drive CB Trip Status Active greater than 44 Vdc Not Active less than 42 Vdc Front Rear Door Switch Active greater than 13...

Страница 27: ...than 11 Vdc Power Fail Monitor Mains Restore greater than 45 1 Vrms Mains Dropout less than 43 1 Vrms DC Voltage Monitors 48 Volt Monitor Active greater than 46 Vdc Not Active less than 44 Vdc 24 Vol...

Страница 28: ...han 164 2 Vrms DC Voltage Monitors 24 Volt Monitor Active greater than 22 Vdc Not Active less than 18 Vdc 12 Volt Monitor Active greater than 11 Vdc Not Active less than 9 Vdc Logic Inputs External Te...

Страница 29: ...200 ms Typical 300 ms Circuit Breaker Trip Fault greater than 400 ms No Fault less than 200 ms Typical 350 ms AC Line Level Sense Fault greater than 750 ms No Fault less than 550 ms Typical 650 ms Fla...

Страница 30: ...c A16 Nreset B16 Nreset A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output R...

Страница 31: ...Rear B28 Reserved A29 Reserved B29 DC MAINS Power A30 Reserved B30 No Connect A31 Equipment Ground B31 Reserved A32 Reserved B32 MAINS Ground Note Output Relay NO is open during FSA de energized 6 2...

Отзывы: