background image

CMU-212 Cabinet Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 6 

2.4 TYPE 62 FSA MESSAGE 

If the “N” bit is set in a Type 62 message, the CMU-212 will react by causing a NFSA. The 

NFSA will remain until the receipt of a Message 62 with the “N” bit cleared or until the 

CMU-212 is reset by a Unit Reset or CMU-212 Power Fail. The NFSA will last for the 

programmed Minimum Flash time at a minimum. 
If the “L” bit is set in a Type 62 message, the CMU-212 will react by causing a LFSA.  

2.5 LACK OF SIGNAL INPUTS MONITOR 

The CMU-212 will detect the absence of a required signal voltage on all the inputs of a 

channel OR the absence of any required channel load current. For voltage purposes a 

required signal on the Green OR Yellow OR Red inputs associated with a channel will be 

considered as that channel being Voltage Active. For load current purposes a total channel 

load current above the programmed threshold for a channel will be considered as that 

channel being Current Active. When a channel is not Voltage Active OR Current Active for 

less than 700 milliseconds, the CMU-212  will not cause a LFSA. When a channel is not 

Voltage Active OR Current Active for greater than 1000 milliseconds, the CMU-212 will 

cause a LFSA. When a channel is not Voltage Active OR Current Active for more than 700 

milliseconds but less than 1000 milliseconds, the CMU-212 may or may not cause a LFSA. 
The Current Sense Unit (CSU) monitor function is hardwired to the maximum of 28 physical 

channels, thus Virtual Channels do not have CSU monitoring capability. The CSU monitor 

function must be disabled for any physical channel that has an input remapped to a Virtual 

Channel.  
Lack of Signal Input monitoring will be disabled for all channels when the MC COIL 

STATUS input is not active. There is programming in the Datakey to disable Lack of Signal 

Input monitoring on a per channel basis. 
Lack of Signal Input monitoring will also be disabled for any channel which has the DARK 

CHANNEL MAP bit set to "1" in the Datakey programming for the DARK CHANNEL MAP 

addressed by the DARK CHANNEL MAP SELECT bits in a Type 61 message. 

2.6 MULTIPLE INPUT MONITOR 

The CMU-212 will detect the presence of an active signal on two or more inputs of a 

channel. When the presence of an active signal on two or more inputs of a channel is 

detected for less than 200 milliseconds, the CMU-212 will not cause a LFSA. When the 

presence of an active signal on two or more inputs to a channel is detected for 450 

milliseconds or more, the CMU-212 will cause a LFSA. When the presence of an active 

signal on two or more inputs to a channel is detected for more than 200 milliseconds but 

less than 450 milliseconds, the CMU-212 may or may not cause a LFSA.  
Multiple Input monitoring may anticipate and prevent a possible conflicting signal display in 

the intersection in the event that a proceed signal on the current phase hangs up and is 

constantly detected as active. An open or no load condition (i.e., burned-out bulb) may be 

also detected as an active signal depending on the output impedance characteristics of the 

load switch (i.e. load switch leakage current), and may cause a Multiple Input Fault. 
Multiple Input monitoring will be disabled when the MC COIL STATUS input is not active. 

There is programming in the Datakey to disable Multiple Indication monitoring on a color 

combination basis (G+Y, Y+R, G+R) for each channel. 

2.7 YELLOW CLEARANCE MONITOR 

The CMU-212 will verify that the Yellow Change interval is at least 2.7 +/-0.1 seconds. The 

Yellow Change interval consists of the duration of time in which the Yellow field signal input 

is active in a sequence from Green to Yellow to Red. When the minimum Yellow Change 

Содержание CMU-212

Страница 1: ...UNIT Firmware Version 2 5 vXX25 REVISION JUNE 2019 pn 888 0212 001 CMU ip 212 ITS Cabinet Monitor Unit Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4 2 OR HIGHER EDI MONITORKE...

Страница 2: ...RODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2019 EDI U S Pat No 7 246 037 Canadian Patent No 2 574 101 U S Pat No 9 460 620 U S Pat No 10 262...

Страница 3: ...Yellow Plus Red Clearance Monitor 7 2 9 Local Flash Status 7 2 9 1 Local Flash Status Recovery 7 2 10 Circuit Breaker Trip Status 7 2 11 Flasher Unit Output Failed Alarm 7 2 12 CMU Power Failure 7 2...

Страница 4: ...us 1 Address Inputs 16 3 7 Serial Bus 1 Disable input 17 3 8 PDA Temperature 17 Section 4 FRONT PANEL DESCRIPTION 18 4 1 Indicators 18 4 1 1 Power Indicator 18 4 1 2 24VDC FAIL Indicator 18 4 1 3 12VD...

Страница 5: ...ITS Standard Specification for Roadside Cabinets Version 01 02 17b document 1 2 CHANNEL CONFIGURATION The CMU 212 can be configured to monitor up to 28 physical load switch channels of three inputs pe...

Страница 6: ...evice using a Personal Computer program such as the Eberle Design MonitorKey product See the Eberle Design MonitorKey Operations Manual pn 888 1212 001 for further details The Datakey is interoperable...

Страница 7: ...60 Module Identification Command Type 188 Module Identification Response Type 61 Load Switch Drivers Command Type 189 CMU Status Response Type 62 Set FSA Command Type 190 FSA Response Type 65 Get CMU...

Страница 8: ...ult conditions causing the NFSA have been removed An NFSA will last for the programmed Minimum Flash time at a minimum Only one LFSA LFSA R or NFSA fault state will be set at any time 1 8 1 EXIT FROM...

Страница 9: ...ill cause a LFSA When any conflicting channels are detected as concurrently active for more than 200 milliseconds but less than 500 milliseconds the CMU 212 may or may not cause a LFSA 2 3 SERIAL BUS...

Страница 10: ...L STATUS input is not active There is programming in the Datakey to disable Lack of Signal Input monitoring on a per channel basis Lack of Signal Input monitoring will also be disabled for any channel...

Страница 11: ...r less than 200 milliseconds the CMU 212 will not cause a NFSA 2 9 1 LOCAL FLASH STATUS RECOVERY Recovery from Local Flash Status NFSA will occur when this signal is sensed as active for greater than...

Страница 12: ...to True high The CMU 212 will then begin timing the programmed Minimum Flash Interval During the Minimum Flash Interval the CMU will be in NFSA 2 12 5 MINIMUM FLASH INTERVAL During the Minimum Flash I...

Страница 13: ...re is Field Check Status then cause of the malfunction can be isolated to the SIU load switch field wiring or signal load When Field Check Status is detected the FIELD CHECK front panel indicator will...

Страница 14: ...uous timing requirements of the normal detection algorithms yet may still produce improper signal displays These input conditions are differentiated by their longer time constant and fault response ti...

Страница 15: ...16 1 1 PROTECTED TURN CHANNEL The Protected Turn Channel of the FYA channel pair is composed of the solid Green arrow Ga indication of the FYA Signal Output Group 2 16 1 2 PERMISSIVE TURN CHANNEL The...

Страница 16: ...e solid Yellow arrow channel clearance are active as determined by the Permissive compatibility programming of the Protected Turn channel Green arrow of the pair 2 16 2 1 2 PERMISSIVE YELLOW CHANGE IN...

Страница 17: ...ill be displayed for the sparse channel Ga 2 16 2 5 YELLOW PLUS RED CLEARANCE The Minimum Yellow Plus Red Clearance function is not designed to operate with Flashing Yellow Arrows This function must b...

Страница 18: ...nflict condition occurs when the Permissive Turn channel flashing yellow arrow sequences to the solid yellow arrow clearance while the Opposing Through channel is still showing a green ball When the F...

Страница 19: ...d The Channel Current Sense Threshold should be programmed for each monitored channel based on the minimum signal load under all worst case conditions 3 3 PDA CONTROL SIGNAL INPUTS 3 3 1 LOCAL FLASH S...

Страница 20: ...SWITCH The cabinet should be wired such that AC is applied to the DOOR SWITCH FRONT or DOOR SWITCH REAR inputs when the respective door is Open These inputs will be considered active door open when th...

Страница 21: ...ror when communications from the ATC is not active When the SERIAL BUS 1 DISABLE input is connected to VDC GROUND True The CMU 212 will not communicate on Serial Bus 1 or set a FSA condition if commun...

Страница 22: ...12 2 4 1 4 CONFLICT INDICATOR A red CONFLICT indicator will illuminate when the CMU 212 is in FSA as a result of a Conflicting Channels fault See section 2 2 4 1 5 LACK OF SIGNAL INDICATOR A red LACK...

Страница 23: ...ing the EDI ECcom Signal Monitor Communications software package See the Eberle Design ECcom Operations Manual for further details This port is electrically isolated from the main CMU 212 power supply...

Страница 24: ...atus FTR Coil Drive CB Trip Status Front Rear Door Switch Active greater than 89 Vrms Not Active less than 70 Vrms Power Fail Monitor AC Line Restore greater than 87 2 Vrms AC Line Dropout less than 8...

Страница 25: ...Check Fault greater than 1600 ms No Fault less than 1400 ms Typical 1500 ms Local Flash Status Circuit Breaker Trip Fault greater than 450 ms No Fault less than 200 ms Typical 350 ms AC Line Level Se...

Страница 26: ...17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output Relay NO A23 CB Trip Statu...

Страница 27: ...key See the EDI ECcom Operation Manual pn 888 1000 001 and MonitorKey Operations Manual pn 888 1212 001 for details The default network settings are IP Address 192 168 1 100 Subnet Mask 255 255 255 0...

Отзывы: