background image

24

Annually

Recommend flue passages, combustion 

chamber area (target wall, fire door insulation, 

durablanket), burner adjustment, control operation, and 

boiler seals (fire door gasket or silicone seal, cast iron 

sectional seals, flue collector) be checked once each year 

by trained Service Technician.

Before start of each heating season

 

(or when 

system has been shut down for extended periods of time) 

recheck whole system for water, oil, and vent piping leaks. 

Replace or patch any leaks or seals that are faulty.

Vent Pipe

: Visually inspect entire venting system 

once a month for any signs of leakage, deterioration, or 

soot build up. If vent pipe shows any signs of leaking or 

deterioration, replace it immediately. If it shows any signs 

of soot build up, clean vent pipe and have burner settings 

and combustion checked by competent professional.

Safety Relief Valve:

 Valve should open automatically 

when system pressure exceeds pressure rating (usually 30 

psi) of safety relief valve. Should valve ever fail to open 

under this condition, shut down the system. Drain system 

until system pressure is reduced below safety relief valve 

pressure rating. Contact Service Technician to replace the 

valve and inspect heating system to determine cause, may 

indicate equipment malfunction. Safety relief valve should 

be tested monthly during heating season. Prior to testing, 

make certain discharge pipe is properly connected to valve 

outlet and arranged so as to contain and safely dispose of 

boiler discharge. Hold trip lever fully open for at least five 

seconds in order to flush free any sediment that may lodge 

on valve seat. Permit valve to snap shut. Refer to valve 

manufacturer’s instructions packaged for more details.
 

Conventional Expansion Tank

: Tank may become 

water logged or may receive excess air. Frequent 

automatic opening of safety relief valve indicates water 

logging. High boiler temperature accompanied by 

unusually low radiation unit temperature (and “knocking” 

noises) indicates excess air in the tank. To correct either 

condition, close valve between boiler and tank. Drain tank 

until empty. Check all tank plugs and fittings, tighten as 

necessary. Open valve between boiler and tank. Water will 

rise to normal height in tank if system has automatic fill 

valve, otherwise manually refill system. 

Diaphragm Expansion Tank

: Tank may become 

water logged. Frequent automatic opening of safety relief 

valve indicates water logging. High boiler temperature 

accompanied by unusually low radiation unit temperature 

(and “knocking” noises) indicates excess air in the tank. To 

correct this condition, replace diaphragm expansion tank.

Water System: 

If system is to remain out of service 

during freezing weather, drain it completely (water left in 

system may freeze and will crack pipes and/or boiler).

Tankless Coil (Or Cover Plate) Gasket:  Check 

gasket at least twice year for leakage, replace if necessary. 

If gasket is replaced, make sure when coil plate (or cover 

plate) is reattached, ten nuts are torqued in alternating 

pattern to insure equal force is applied to entire gasket 

creating good seal. Nuts should be torqued so gasket does 

not squeeze out from behind the plate.

Control Well:

 

Remove control well every five years and 

clean any scale or sediment deposits from all parts exposed 

to boiler water.  After cleaning, reinstall well using pipe 

sealing compound. Teflon tape is not recommended.

Oil Burner Maintenance

Perform following preventative maintenance annually, prior 

to heating season is preferred.

1. 

Do not oil- Oil burner motors are permanently 

lubricated.

2. 

Fuel Filter- Replace to prevent contaminated guel from 

reaching nozzle.  Partially blocked fuel filter can cause 

premature failure of fuel pump.

3. 

Fuel Pump Unit- Replace pump screen and clean 

pump unit to maintain fuel delivery to nozzle.

4. 

Ignition Electrodes - Clean and adjust per 

manufacturer’s recommentdations, to maintain reliable 

ignition of oil.

5. 

Nozzle- Replace to maintain safe and reliable 

combustion efficiency. Replace with nozzle as required 

in charts located in this manual.

6. 

Fan and Blower Housing- 

 Must be kept clean, free 

of dirt, lint and oil to maintain proper amount of air fuel 

requires to burn.

7. 

Check Final Burner Adjustments.

Never burn garbage or paper in the unit, never leave 

combustible material around it.

MAINTENANCE

 WARNING

Burn and scald hazard.  Do not attempt to start 

the burner when excess oil has accumulated, when 

the unit is full of vapor, or when the combustion 

chamber is very hot. Failure to follow these 

instructions could result in death or serious injury.

!

     

 PN 240013023, Rev. B [12/31/2020]

Содержание Utica Keystone UH3KWC0.80

Страница 1: ...STALLATION OPERATION MAINTENANCE MANUAL Model UH3KWC0 80 T UH4KWC1 00 T UH4KWC1 25 T UH5KWC1 55 T Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com PN 240013023 REV B 12 31 2020 ...

Страница 2: ...se low pressure oil fired hot water boilers are constructed and hydrostatically tested for maximum working pressure of 50 psig pounds per square inch in accordance with the latest revision of the A S M E American Society of Mechanical Engineers Boiler and Pressure Vessel Code Section IV Standards for heating boilers Heating Capacity indicates amount of heat available after subtracting losses up th...

Страница 3: ... 132 8 x8 x15 86 0 17 3 4 6 9 5 8 UH5KWC1 55 T 5 1 55 217 189 164 8 x8 x15 86 0 21 6 11 1 2 MBH 1 000 Btu Per Hour BTU British Thermal Unit Heating capacity based on 13 1 CO2 with 0 02 W C draft over fire and 1 smoke or less Testing was done in accordance with D O E Department Of Energy test procedure GPH Gallons Per Hour Of Oil At 140 000 Btu Per Gallon A F U E Annual fuel utilization efficiency ...

Страница 4: ...anent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in bathtub or shower Never allow small children to use a hot water tap or draw their own bath If anyone using hot water in the building fits the above description or if state laws or local codes require certain water temperatures at hot water...

Страница 5: ...g the boiler Boiler manufacturer recommends initial fill pressure of 10 12 psig For higher fill pressures expansion tank s air charge will need to be increased to match fill pressure Consult manufacturer s guidelines for sizing and selection 13 Purging heating system of air and gases when first placing boiler into service is critical for proper circulation and quiet performance Once air and gases ...

Страница 6: ...such attention Boilers must be installed at least 6 from combustible material on left side rear and above and at least 24 on right side and front Allow 24 accessibility clearance above for servicing 5 Fresh air for combustion must be available at front of the boiler Fresh air for ventilation must be available to front and rear of boiler Air passages must be free of obstructions at all times Ventil...

Страница 7: ...N TANK AUTOMATIC FILL VALVE AND SHUTOFF RELIEF VALVE TO RADIATION FROM RADIATION CIRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL PIPE MIN 2 I D VENT PIPE ENTRANCE SWITCH OIL BURNER GENERAL PRINCIPAL REQUIREMENTS FOR A TYPICAL INSTALLATION within 6...

Страница 8: ...with additional room s of sufficient volume so that combined volume of all spaces meets criteria for unconfined space Total input of all combustion equipment installed in combined space shall be considered in making this determination Each opening shall have minimum free area of one square inch per 1 000 Btu per hour of total input rating of all combustion equipment in confined space but not less ...

Страница 9: ...osure 3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in the enclosure 4 When ducts are used they shall be of same cross sectional area as free area of openings to which they connect Minimum dimension of rectangular air ducts shall be not less than three inches FRE...

Страница 10: ...ler See figures 6a and 6b A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install discharge piping from safety relief valve Use or larger pipe Use pipe suitable for temperatures of 375 F 191 C or greater Individual boiler discharge piping shall be independent of other discharge piping Size and arrange discharge...

Страница 11: ...lly cause damage to boiler and venting system Minimum design return water temperature to prevent this condensation in boiler and venting is 120 F Boiler used in heating system where design water temperatures below 140 F are desired e g radiant floor heating a 3 way or 4 way mixing valve or suitable alternative e g Bypass Piping Arrangement as shown in Figure 7 is required to prevent low temperatur...

Страница 12: ...OR MAY ALSO BE INSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 8 System Piping Arrangement Zoning With Zone Valves PN 240013023 Rev B 12 31 2020 ...

Страница 13: ...OR CAN ALSO BE INSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Arrangement Zoning With Circulators PN 240013023 Rev B 12 31 2020 ...

Страница 14: ...NG PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS Figure 10 System Piping Arrangement Alternate Near Boiler Piping SYSTEM PIPING PN 240013023 Rev B 12 31 2020 ...

Страница 15: ...s also recommended as shown in figure below Flow restrictor may be required on tankless coil inlet piping so flow rates are matched to boiler heat input see table SYSTEM PIPING Tankless Coil Piping Arrangement Figure 11 Tankless Coil Piping Arrangement DANGER Scald Burn Hazard Temperatures exceeding 120 F will cause severe burns or death Use of water tempering device or mixing valve may be require...

Страница 16: ... SIZES FIRING RATE gph CHIMNEY HEIGHT ft NOMINAL CHIMNEY ROUND LINER INSIDE SQUARE LINER INSIDE 0 60 1 30 15 8 x 8 6 6 x 6 1 35 1 80 15 8 x 8 7 6 x 6 For elevations above 2 000 feet above sea level add 3 feet to the chimney heights For oil fired boilers for connections to vents or chimneys vent installations shall be in accordance with applicable provisions of NFPA 31 Standard for the installation...

Страница 17: ...r requires 6 diameter chimney connector pipe and use of manufacturer provided draft regulator Regulator when properly installed automatically controls the draft Install in horizontal section of pipe may also be installed in angled or vertical section of pipe Verify top of regulator is at the top and short pipe section which holds the vane is horizontal Even though locating draft regulator close to...

Страница 18: ...r national state or local codes or regulations Connect 120 volt electrical supply to L1 and L2 terminals and two thermostat wires to T and T terminals on Hydrolevel limit control Run separate circuit from separate over current protection device in your electrical service entrance panel Minimum 15 ampere circuit Locate shutoff switch at boiler Turn off during any maintenance Solder and tape or secu...

Страница 19: ...19 ELECTRICAL WIRING Figure 13 Boiler With Hydrolevel 3250 Control PN 240013023 Rev B 12 31 2020 ...

Страница 20: ...r purging drain valve runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain valve and fill line shut off valve open main shutoff valve and adjust throttling valves and balancing valves as required OPTION 2 Close air vents on all radiation units Open valves to radiation u...

Страница 21: ...air burner flame will be dark orange and formation of soot will occur in heating unit In buildings of conventional frame brick or stone construction that do not have utility rooms basement windows or stair doors air infiltration is normally adequate to provide enough air for combustion and for operation of barometric draft control Room used for supplying combustion air should be isolated from any ...

Страница 22: ...le V1 Head Adjustments and Settings BECKETT AFG BOILER MODEL BURNER MODEL INPUT RATE gph INSERTION DEPTH DELAVAN OIL NOZZLE PUMP PRESSURE psi LOW FIRE BAFFLE BURNER HEAD HEAD SETTING AIR SHUTTER BAND STATIC PLATE UH3KWC0 80 T AFG50MBAS 0 80 2 1 4 0 65 70 W 150 YES L1 N A 10 1 3 3 8 UH4KWC1 00 T AFG50MDASN 1 00 2 1 2 0 85 60 A 140 NO V1 0 6 1 2 3 4 UH4KWC1 25 T AFG50MDASN 1 25 2 1 2 1 00 60 W 155 N...

Страница 23: ...n chamber is very hot Adjust Thermostat Heat Anticipator or Thermostat Cycle Rate According to Instructions Included With The Thermostat Check Thermostat Operation Follow instructions included with your thermostat Locate thermostat five feet above the floor on inside wall Locate thermostat to sense average room temperature avoid the following THERMOSTAT LOCATIONS TO AVOID DEAD SPOTS HOT SPOTS COLD...

Страница 24: ... will rise to normal height in tank if system has automatic fill valve otherwise manually refill system Diaphragm Expansion Tank Tank may become water logged Frequent automatic opening of safety relief valve indicates water logging High boiler temperature accompanied by unusually low radiation unit temperature and knocking noises indicates excess air in the tank To correct this condition replace d...

Страница 25: ...When brushing take care not to damage target wall with flue brush See figure 16 6 Carefully vacuum soot accumulations from combustion chamber area be careful not to damage any refractory or blanket insulation To gain access to combustion chamber first double check the shut off valve on fuel oil line is closed and disconnect fuel oil line Remove oil burner from fire door Remove fire door 7 Inspect ...

Страница 26: ...ner being used has damaged head replace head with same head recommended for use on this boiler 6 Inspect and clean oil burner blower wheel 7 Remove oil pump cover and clean replace pump screen Carefully reassemble ensuring pump cover makes proper seal 8 Securely fasten oil burner to fire door 9 Replace fuel filter if applicable 10 Reconnect electrical and fuel supplies 11 Fire burner checking for ...

Страница 27: ... be in closed position Circulating pump not running Check over current protection Check relay operation Poor electrical contact Check all control terminals and wire joints Chimney flue is blocked Have the chimney professionally cleaned Circulator running when boiler water temperature is below low limit set point tankless coil boilers only Honeywell L7248L control confirm ELL parameter on L7248L co...

Страница 28: ... decreases This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not use...

Отзывы: