ENVIROAIR DUCTLESS SPLIT SYSTEMS

SINGLE AND MULTI-ZONE

P/N# 240-4372, Rev. 2.4 [08/04]

An ISO 9001-2000 Certified Company

INST

ALLA

TION MANUAL

 AND OPERA

TING INSTRUCTIONS

SINGLE ZONE

COOLING ONLY

ACW-09D-B – CCW-09D-B
ACW-12D-B – CCW-12D-B
ACW-18D-B – CCW-18D-B
ACW-24D-B – CCW-24D-B

COOLING AND HEATING

AHW-12D-B – CHW-12D-B
AHW-18D-B – CHW-18D-B
AHW-24D-B – CHW-24D-B

MULTI-ZONE

COOLING ONLY

ACM-09D-B – CCM-09D-B
ACM-12D-B – CCM-12D-B

COOLING AND HEATING

AHM-09D-B – CHM-09D-B
AHM-12D-B – CHM-12D-B

ENVIROMASTER INTERNATIONAL LLC

5780 Success Drive
Rome, NY 13440
Ph: (800) 228-9364
Fax: (800) 232-9364

www.enviromaster.com

Содержание EnviroAir ACM-09D-B

Страница 1: ... 09D B CCW 09D B ACW 12D B CCW 12D B ACW 18D B CCW 18D B ACW 24D B CCW 24D B COOLINGANDHEATING AHW 12D B CHW 12D B AHW 18D B CHW 18D B AHW 24D B CHW 24D B MULTI ZONE COOLINGONLY ACM 09D B CCM 09D B ACM 12D B CCM 12D B COOLINGANDHEATING AHM 09D B CHM 09D B AHM 12D B CHM 12D B ENVIROMASTER INTERNATIONAL LLC 5780SuccessDrive Rome NY 13440 Ph 800 228 9364 Fax 800 232 9364 www enviromaster com ...

Страница 2: ...odes Do not modify the system s It may increase the risk of fire SAFETY TIPS FOR OPERATION CAUTION DEODORIZING FUNCTION In case of DRY and COOL mode the fan or indoor unit s will not turn ON for 40 seconds even after starting the operation in order to deodorize various smells emitting from the inside of indoor unit Never expose infants handicapped persons or seniors directly to the airflow Adjust ...

Страница 3: ...During the season set the Hand Switch Lever to ON I position After the season set the Hand Switch Lever to OFF O position Hand Switch Lever The Remote Control is stored inside the product Please open the front grill to remove the Remote Remote Control Storage Air Intake Left side Rear Drain Hose Air Outlet Interconnection cable pipes and power supply Air Outlet Drain Hose Air Intake Left side Rear...

Страница 4: ...g Do not let children play with the Remote Control To avoid interference the indoor unit and the Remote control unit should be at least 3 feet away from a TV set or a radio In cases where than two air conditioners are installed in the same room individual operation may not be possible Transmitter Low Battery Indicator Display Window ON OFF Button Temperature Setting Button High Power Button One Ho...

Страница 5: ...or CIRCULATE mode as you wish 1 Press the MODE button on the Remote Control Cold weather High humidity Hot weather When air circulation is needed HEAT mode DRY mode COOL mode CIRCULATE mode 2 Press the ON OFF button When the fan speed or air flow direction is to be changed When the set temperature is to be changed Room Temperature Over 27 C 81 F 20 27 C 68 81 F Below 20 C 68 F Operating Mode Cool ...

Страница 6: ...to the contaminating status of air filter In this case please clean or replace the air filter with a new one OPERATION Continued FAN SPEED AIR FLOW DIRECTION To operate the unit s effectively it is recommended that you familiarize yourself with the following functions To change the fan speed Press the FAN SPEED button Cold air moves down horizontal air flow is preferred when cooling To change the ...

Страница 7: ...en the HIGH POWER mode button is pressed heated or cooled air comes into the room at a higher fan speed for 15 minutes The fan speed changes rhythmically between high and ultra high When the air conditioner s continue to run on HIGH POWER mode in a large room they may not reach the set room temperature due to limited cooling capacity This may cause water drops to form around the outlet In such cas...

Страница 8: ... pressing the 1HR TIMER button again during the ONE HOUR TIMER mode the unit will stop operation ap proximately one 1 hour later The ONE HOUR TIMER mode has preference over other Timer modes If pressing the 1HR TIMER button again during the OFF TIMER mode the unit s will stop operat ing approximately one 1 hour later EMERGENCY OPERATION When the remote control cannot be used due to dead batteries ...

Страница 9: ...hinner and cleaning powder may damage the coated surface or the plastics Do not use water higher than 40 C 104 F or the air filters may shrink and the plastic materials may be dam aged Do not touch the evaporator coil when removing and re placing the air filters Injury may occur Never operate the unit without the air filters 1 CLEANING AIR FILTERS ONCE EVERY TWO WEEKS Clean the air filters at leas...

Страница 10: ... please put the switch lever s on the indoor unit s in off O position 18 24 Btuh Blinking Green LED Red LED Green LED Defect of indoor heat exchanger sensor Defect of compressor protection circuit Cooling only Model Trouble Check by Self Test Mode Contents of Defect Defect of room temperature sensor PLEASE CHECK THE FOLLOWING THE UNIT S WON T OPERATE Check the batteries in the Remote Control Check...

Страница 11: ...r Cushion 18 24 Btuh Rubber Cushion 3 Drain Pipe 1 1 2 Parts of Indoor Unit Parts of Outdoor Unit 4 4 Be sure chosen location can properly support the weight of the unit s and will provide adequate damping of vibration and noise Outdoor Unit Insure chosen location can provide adequate drainage and good ventilation Do not install in an area with flammable or corrosive vapors Avoid salty air or sulf...

Страница 12: ...t the installation plate horizontally and securely on structural members studs etc in the wall with four 4 installing screws See Fig 1 3 Make a 2 9 16 hole through the wall Hole should be angled down to the exterior See Fig 2 4 Use a city grade wall pipe outer diameter 2 3 8 as a sleeve to protect the interconnection cable and the pip ing See Fig 2 When inserting the pipes protect the ends from du...

Страница 13: ...G OF THE OUTDOOR UNIT 1 Remove the cap from the service port on the suction line service valve 2 Connect the suction side of the refrigerant gauge manifold to the Suction Line service valve Connect the center hose of the refrigerant manifold gauge to the micron gauge Connect the other side of the micron gauge to the vacuum pump Diagram 1 3 Open the suction side of the refrigerant manifold set and ...

Страница 14: ...6 of the rated voltage marked on the indoor unit label s Connect one end of the ground wire to the outdoor unit ground terminal Use minimum 14 AWG wire conductors between the in door and outdoor units Refer to page 16 to determine the wire size from the power supply to the condenser Make sure wire connections are secure otherwise elec trical malfunction may occur Cool and Heat Model ENVIROAIR ELEC...

Страница 15: ...9 12 Btuh Single or Multi Zone Be sure to check the power source then turn the power on Check the installation again First set the lever to OFF O position then to ON I and TEST position slowly During the test the indicator light will blink 18 24 Btuh 9 12 Btuh 1 Wiring between units should be cut to length 2 Remove the wiring cover of the Indoor Unit s and the Outdoor Unit 3 Insert the connection ...

Страница 16: ... F Single Zone System Cooling Capacity SEER Heating Capacity Btuh 2 Max Fuse HSPF Volts HZ Phase Total Amps MCA Nominal 5 Sensible AMPS HP RLA LRA AMPS HP EMCW18000 1 18 000 12 600 10 9 208 230 60 1 0 72 0 2 4 45 26 0 22 0 06 10 1 11 1 15 197 EMHW18000 2 17 400 11 700 10 0 17 700 6 8 208 230 60 1 0 72 0 2 4 45 26 0 22 0 06 10 1 11 1 15 197 EMCW24000 3 24 000 15 500 10 6 208 230 60 1 0 72 0 2 5 85 ...

Страница 17: ...86 80 5 5 75 Room Temp F 5 0 4 5 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Outdoor Fan Speed Low Pressure PSI Outdoor Fan Speed Room Temp F Low High Low High 99 85 86 80 71 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 12 86 10 80 75 8 Room Temp F 6 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Outdoor Fan Speed Low Pressure PSI Outdoor Fan Speed Room Temp F Low H...

Страница 18: ...Enviromaster International LLC Enviroair Ductless Split System 18 OPERATING CHARACTERISTICS Single Zone Heating All units operating on high speed fan EHW12000 EHW18000 EHW24000 ...

Страница 19: ...6 71 80 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 5 86 4 5 80 75 4 Room Temp F 3 5 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Low Pressure PSI Room Temp F 99 85 86 71 80 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 8 7 Room Temp F 86 6 80 75 5 4 68 77 86 95 104 Outdoor Intake Temp F Running Current A Low Pressure PSI Room Temp F THERMISTER CHARACTER DIAGRAMS ...