36
Verify Burner, Proper Operation
1.
Inspect burner flame through Sight Glass. See
figure 9-5.
2.
Operate boiler through several heating cycles,
including domestic hot water, if used. Verify proper
operation.
3.
Reset control parameters to operating settings if
adjusted to allow startup and operation test.
4.
Follow instructions TO TURN OFF GAS TO APPLIANCE
if boiler is not being placed into immediate operation.
5.
Enter installer information on Warranty Registration
Card.
6.
Gather all instructions, manuals, wiring diagrams,
warranty registration card and other supporting
information. Review with user and/or affix in
conspicuous location adjacent to boiler.
Gas
CO
2
CO
Min.
Max.
Natural Gas
9.0
9.5
<200ppm
Propane
10.0
11.0
<200ppm
NOTICE
Contact Technical Support @ 800-325-5479 for
additional information or assistance.
Natural Gas only**
1.
Measure input. Compare to table above. Continue
to measure input and CO
2
until both measured
values are within range specified in tables
.
Propane Gas
Most propane systems do not have flow meters.
1.
Check CO
2
. Propane should be between 10% and
11.0%.
•
If CO
2
is low increase gas flow following figure
9-3 & 9-4.
•
If CO
2
is high decrease gas flow following figure 9-3
& 9-4.
9 - START UP PROCEDURE
FIGURE 9-3 Gas Valve - Models 075/100 MBH
1/4" Flat Head
Screwdriver
• To increase gas flow turn 'throttle' left or counter
clockwise
.
• To decrease gas flow turn 'throttle' right or
clockwise .
•
Limit adjustment to one turn and retest.
Содержание 075 97gb
Страница 44: ...44 13 TROUBLE SHOOTING ...
Страница 48: ...48 13 TROUBLE SHOOTING ...
Страница 50: ...50 13 TROUBLE SHOOTING ...
Страница 61: ...61 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Страница 62: ...62 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Страница 78: ...78 NOTES ...
Страница 79: ...79 Company Address Phone Company Name Tech Initials Service Performed Date ...