6 - COMBUSTION AIR AND VENT PIPING
C. Double Line System
This system consists of boilers installed on two lines,
connected to a common exhaust manifold.
2 in. per 3 ft. 4 in.
(50.0 mm per 1.0 m)
3°
6.13 Multiple Boiler Venting - Parameter Settings
To set parameter
P19
see section 9 to ensure check valve in
vent opens.
PARAMETER P19
Revs/min (rpm) at minimum Power
Natural Gas (A)
LPG (E)
30
30
Flue header size shall be calculated by qualified service agency
during system design as required by local authority having
jurisdiction.
FIGURE 6-29 - Multiple Boiler Vent Applications
PN 240011662 Rev. H [04/30/2019]