SPECIFICATIONS

 

Frequency: 433.92MHz 

Operating Temperature: 32°-120°F (0°-49°C)   

Battery: One 3Vdc lithium CR123A 

Operating Humidity: 5-95% RH non condensing   

Battery life: 5 years 

Compatible with 433MHz ClearSky Security Systems 

 

Detection distance: 6 in max 

Supervisory signal interval: 70 min(approx.) 

 

Maximum current draw:  23mA during transmission 

 

OPERATION

 

The FireFighter™ sensor is designed to listen to any smoke, carbon or combo detector. Once confirmed as an 

alarm,  it will transmit a signal to the alarm control panel which if connected to a central monitoring station, will 

dispatch the  fire department.

 

WARNING: This audio detector is intended only for use with smoke, carbon and combo detectors but it does 

not detect the presence of  smoke, heat, or fire directly.

 

 

ENROLLING  

To enroll the sensor remove the top cover by depressing the friction tab in order to reveal the 
battery.  Pull and discard the battery plastic tab to turn on the device.  
 
Download and install ClearSky App on your android or IOS phone. 
Open your 

ClearSky APP and follow the directions on the app to learn in the sensor.  

App will require you to press the learn button when linking (Image 1). 

There are 2 modes of detection on the FireFighter

.  Mode 1 is smoke only and Mode 2 is smoke and 

carbon monoxide alert detection.  To switch between modes, remove the battery, press and hold 
the tamper switch and learn button until a red LED turns on.  Let go of tamper and learn button.  1 
red blink indicates smoke alert detection.  2 red blinks indicates smoke + CO alert detection. 

 
 

MOUNTING 

 

Included with this device is a mounting bracket, hardware and double sided tape. To ensure proper 
operation  ensure the side of the device with the small holes is directly facing the sounder holes on the smoke 
detector. Secure  the mounting bracket to the wall or ceiling using the two mounting screws and double 
sided tape provided, then  secure the audio detector to the mounting bracket using the small screw 
provided. The FireFighter™ must be mounting  within 6 inches of the detector for optimal operation.

 

WARNING: Non-interconnected smoke detectors require an audio detector by each smoke detector sounder. 

This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 
72, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing 
proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided 
with this equipment. Warning: Owner’s instruction notice: ’Not to be removed by anyone except occupant’. 
 

 