ESI (Ultra) Service Manual
60/68
NOTE: Normal resistance for compressor
3-phase resistance (UV, UW, VW) for compressor is
less than 5Ω.
The insulation resistance (any phase to Ground) for
compressor is greater than 100KΩ.
Display
or
Compressor INV module
protection
YES
NO
YES
NO
NO
YES
YES
NO
YES
NO
Turn off the power supply to replace the main control board.
Restart the unit, does the error code disappear?
NO
YES
Back to normal
Replace the compressor
Clean the terminal
Are there any dirty things on the compressor terminal?
Replace the compressor
Is the compressor open-circuited?
*NOTE
Reconnect the wiring
Are the compressor wirings (U/V/W) securely connected?
Replace the indoor coil
Has the micro channel coil been used for heat pump?
The power supply voltage is not in the range of 187~253VAC.
Contact power supply agency to
verify that they are sending the
correct voltage.