Manufacturer reserves the right to change specifications or designs without notice.
10.2019
ESI (Ultra) Service Manual
57/68
1.
Error definition:
The defrost temperature (TH) sensor is short circuit or open circuit.
2.
Possible causes:
Damaged main control board
The defrost temperature sensor is wrongly seated
Temperature sensor failure
There are other heat sources around the sensor
NOTE: Measure the DC voltage of the temperature sensor also works when outdoor unit powers on.
Display
Defrost temperature (TH) sensor is
disconnected or damaged
Check whether TH sensor is seated to the specified location and
NO
connected to
CN4
on the main control board.
YES
Turn off the power supply, unplug the TH sensor to check if the
resistance is in the range of
Temperature sensor A
. *
NOTE
NO
YES
YES
NO
YES
NO
Replace the main control board
Replace the sensor
Can the system go into backup running (SEG1 displays digital 6)?
Remove other heat source
Are there any other heat sources around the sensor?
Replace the sensor
Reconnect the sensor