1.
Error definition:
•
The fan rotation speed is less than 240RPM if it has the running signal.
•
The rotation speed difference between the detected value and target one is over 200RPM for
3 minutes.
2.
Possible causes:
Damaged main control board
Malfunction of fan motor
The unit is undergoing hurricane
Disconnected wiring between fan motor and main control board
NOTE: The normal working state of IoT device should be blue LED
(No.1) is blinking with other LEDs are off.
LEDs
Display
DC fan motor over-load protection
Had the IoT device successfully communicated with Ecoer cloud
after installation?
*NOTE
NO
YES
YES
NO
NO
YES
Turn off power supply for at least five minutes, use tools to rotate
fan blades manually to check if the motor shaft is stuck.
YES
NO
Replace the main control board
Replace the motor
Connect the cable
Is the fan motor cable connected to
CN8
on main control board?
Waiting for the wind to decrease
Is the fan speed higher than 200RPM on stop/standby condition?
Make sure the IoT device works
properly.