ESI (Ultra) Service Manual
5/68
TL
EEV
FAN
TH Heat Exchanger
Gas Service Valve
ST1
Gauge Port
TD
INV
TS
ACC
HP
LP
2.1.2
Major Components Functions and Refrigerant Circuits Diagram
Liquid Service Valve
TA
Name
Symbol
Function
Inverter compressor INV
Adjusts refrigerant flow rate by changing the compressor speed (RPS)
based on objective pressure.
DC motor
FAN
Outputs heat exchanger capacity by adjusting the motor rotation speed
based on operating pressure.
Electronic expansion
valve
EEV
1)
Fully open during cooling mode and defrost operation.
2)
Control compressor discharge superheat in heating mode.
Reversing valve
ST1
Switches the operation mode between heating and cooling (including
defrost control).
Temperature sensor
TH
Uses to control defrosting during heating operation.
TA
Uses to detect outdoor air temperature and control fan speed.
TS
Uses to detect compressor suction temperature and calculate compressor
suction superheat (SH).
TL
Uses to detect liquid line temperature and calculate sub-cooling (SC).
TD
Uses to detect compressor discharge temperature and calculate
compressor discharge superheat (DSH).
TF
Uses to detect heat sink temperature of inverter module.
High pressure sensor HP
Uses to detect high pressure.
Low pressure sensor LP
Uses to detect low pressure.
Accumulator
ACC
Uses to store excess refrigerant.