ESI (Ultra) Service Manual
19/68
Default mode
(Press
BS3
button to
query operation data)
2.3.2
Setting by dip switches
Condensing units’ functions can be applied by dipping switch and pressing buttons.
Use minor straight
screwdriver to dip switch.
Power off the unit for at
least two minute to
activate the change.
* Keep OFF (factory) when EODA18H-4860 matches with 2 or 3 Ton indoor unit for hyper heating.
2.3.3
Setting by pressing buttons
Query and setting operation can be done by pressing buttons on main control board.
SEG1
SEG2 SEG3
Off
Blinking
On
BS1
: Menu or back button
BS2:
UP button
BS3:
Spot check and confirm button
BS1
BS2
BS3
Press buttons
Remarks: Press or tip any directions are valid.
Press and hold BS1for 5 seconds
to set special functions.
Press
BS1 once
to query
current setting.
Setting mode
Query setting mode
Symbol selection by
pressing
BS2
button
Press BS3
Setting item selection
by pressing
BS2
button
Press BS3
Contents display
Press BS3
Symbol selection by
pressing
BS2
button
Press BS3
Contents display
Press BS3
SW1
ON
DIP
1 2 3 4
SW1 dip switch
Description
NO
.
Setting item
Status
Content
1
Reserved
-
-
2
Capacity selection
*
ON
2 or 4 Ton
OFF (factory)
3 or 5 Ton
3
AC only/Heat pump selection
ON
AC only
OFF (factory)
Heat pump
4
Demand response to IoT
ON
No
OFF (factory)
Yes