ESI (Ultra) Service Manual
12/68
HP≥C
HP<D
HP<D
HP≥B
Upper limit compressor
After 15 sec.
HP≥B
HP≥A
High pressure abnormal standby
Upper limit compressor step = Current step
Normal operation
(Upper limit compressor step = Max. step)
2.2.3.
Protection controls
2.2.3.1
High pressure protection control
High pressure (HP) protection control is used to prevent extremely high pressures in the system and
protect the compressor.
step: Decrease 2step
Current step maintained
and
HP<D
Restart permission=ON
Symbol
EODA18H-2436/4860
Cooling
Heating
A
545psig [3.8MPa]
545psig [3.8MPa]
B
493psig [3.4MPa]
479psig [3.3MPa]
C
479psig [3.3MPa]
450psig [3.1MPa]
D
464psig [3.2MPa]
421psig [2.9MPa]
Compressor restarts